Regulated NAC Outputs
NAC outputs of the Elite-RS Panel operate in a regulated mode when conforming to specific levels of
continuous or pulsed DC. NAC outputs meet requirements for regulated levels when the output current does not
exceed the constraints described below:
Regulated Continuous Output Current
Continuous DC currents cannot exceed 1.6 A from either NAC output when operating in a regulated output mode:
Regulated continuous DC output = 1.6 A
NAC 1
+ 1.6 A
NAC 2
= 3.2 A total
Regulated Pulsed Output Current
Pulsed DC currents cannot exceed 900 mA from either NAC output when operating in a regulated output mode:
Regulated pulsed DC output = 900 mA
NAC 1
+ 900 mA
NAC 2
= 1.8 A total
Reference Appendix A, Specifications for operating NAC outputs in the regulated mode.
Synchronization Modules
Synchronize the regulated output of NAC 1 and NAC 2 using UL listed and compatible synchronization
modules. Connect End-Of-Line-Device VF1539-00 to the output of each Synchronization Module installed.
Operating the NAC outputs of the Elite-RS Panel in a regulated output mode requires the use of external
synchronization-modules when performing synchronization. Notification Appliances and Synchronization Modules
are described in the table below for regulated NAC outputs of the Elite-RS Panel:
*** All NAC devices determined to be compatible with the synchronization modules above are compatible for
operation with the Elite-RS Panel.
Manufacturer
Manufacturer
Sync Module
VES
Sync Module
Manufacturer
and VES NAC
Device
Maximum NAC
Load
System Sensor
MDL (Red)
MDLW (White)
VF6012-10 (Red)
VF6012-30 (White)
***
0.90 A
Wheelock
SM-24-R
DSM-24-R
VF6009-10 (Single)
VF6010-10 (Dual)
***
0.90 A
Amseco
SMD10-3A
VF5000-00
***
0.90 A