Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
22 of 146
Before Wiring and Operating
The 5.25 Amp power supply of the Elite-RS Panel provides settings for voltage inputs of 120 VAC or
240 VAC. Check these input settings prior to wiring and operating the control panel. Make certain that the power
supply setting is 240 VAC before applying a 240 VAC input.
Permanent damage to the power supply will occur if the input setting is 120 VAC and a 240 VAC input is applied.
Remove jumper J1 from the circuit-board of the power supply to provide 240 VAC operation. Connect jumper J1 to
the circuit-board to provide 120 VAC operation.
The figure below illustrates the location of jumper J1 on the circuit-board of the Elite-RS Panel:
Figure 3-13
Circuit-Board Jumper J1
WARNING!
Remove jumper J1 before operating the Elite-RS Panel at 240 VAC. Failure to remove jumper J1 before
240 VAC operation will cause severe and permanent damage to Elite-RS components.
WARNING
HIGH
VOLTAGE
D1090 ISSUE 01
FUSE
5X20
REMOVE JUMPER J1 TO
OPERATE THE POWER
SUPPLY AT 240 VAC.