Maintenance and Repair 5
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
58 of 146
Replacing Fuses
A 10 Amp battery fuse and a 3 Amp power-supply fuse are provided to protect the Elite-RS Panel against circuit
overloads. During the life of the product it may be necessary to replace one or both of the fuses to restore operation to
the Elite-RS Panel.
Replace a fuse only after replacing the components responsible for causing the fuse failure. Fuse failure is not a
condition caused by the fuse. Diagnose and replace components in the fuse-circuit before replacing the fuse and oper-
ating the Elite-RS Panel.
10 Amp Battery Fuse
Replace the 10 Amp battery-fuse by removing the fuse, the battery wiring and the standby-batteries.
Specify kit VF1548-00 to replace the red-cable containing the 10 Amp fuse or specify battery-lead-kit VF1514-00 to
replace the red-cable containing the 10 Amp fuse, the jumper-cable and the black-cable.
Replace the 3 Amp Power-Supply Fuse by removing it from the housing contained on the circuit board of the
power supply. Install the replacement fuse in the housing and then test the power supply to determine that it operates.
Removing the 10 Amp Battery-Fuse
To remove the fuse:
Installing the 10 Amp Battery-Fuse
To install the new 10 Amp Battery-Fuse:
1
Remove the battery-connector from the Battery Connection on the front-panel of the Elite-RS.
2
Disconnect the jumper-cable connection between Battery 1 and Battery 2.
3
Disconnect the red-cable from the positive terminal of Battery 1.
4
Disconnect the black-cable from the negative terminal of Battery 2.
5
Dispose the battery-leads described in steps 1 through 3 above.
1
Connect the jumper-lead from the negative terminal of Battery 1 to the positive terminal of Battery 2.
2
Connect the red-cable to the positive terminal of Battery 1.
3
Connect the black-lead to the negative terminal of Battery 2.
4
Connect the battery-connector to the Battery Connection on the front-panel of the Elite-RS.
5
Determine that trouble conditions are not reported by the Elite-RS Panel following the fuse replacement.
This step will confirm if the installation was performed correctly.