Testing the Installation
Perform the following before testing the Elite-RS Panel:
Confirming a Successful Installation
The Elite-RS Panel installation is successful when it completes the following sequence of front-panel displays:
The front-panel displays shown are intended for reference only.
Panel initialization
1
Connect loops, sounder circuits, inputs and outputs to the control panel.
2
Confirm that correct connections exist between the batteries and the power supply.
3
Apply AC power to the Elite-RS Panel.
4
Verify that the panel display illuminates.
5
Perform an AUTO LEARN and confirm that the Front-Panel Menu does not contain errors.
AUTO LEARN is a feature of the Elite-RS Panel for testing the health of external devices and connections.
Operate AUTO LEARN through Access Level 3 of the front-panel menu. External devices receive default
configuration settings during the AUTO LEARN sequence and circuit connections are tested for opens, shorts
and ground fault conditions.
6
Test the Elite-RS Panel lamps.
1
Panel Initialization
Tests internal hardware and firmware responsible for operating loop devices.
2
Loop Initialization
Configures the Elite-RS Panel to existing loop conditions.
3
Normal-Standby
Displays the Normal Standby after a successful boot process.
CAUTION!
The Elite-RS Panel buzzer may activate following AUTO LEARN. Buzzer activation indicates that an
installation error condition exists. Disable the buzzer after determining the cause of the alarm and then
rectify the installation problem.
Fire
AC Power On
Pre-Alarm
On Test
More Events
Point
Bypassed
General Trouble
Power Trouble
Supervisory
NAC Trouble
Panel
Sounder
Silenced
Delay Active
INITIALIZING PANEL
PLEASE WAIT...
Programmable
Function
Enable Access
Alarm
Silence
Panel Sounder
Silence
Lamp
Test
Reset
Fire Drill
Re-Sound
Alarm
1
2
3
4
?
More
Events
More
Fire Events
Enter
Exit