Split System Indoor Unit:
VRC202KIT
Cooling capacity
0.9 - 3.5 kW
Air Volume
750 m³/h
VRC Input
Hardwired L+N+PE
Voltage, Frequency
230 Vac , 50/60 Hz
Full Load Amperage (FLA)
1,5 A
Refrigerant type (pre-charged)
R410A, indoor unit 400 g (0.88 lb)
VRC Form Factor
6U
VRC-S Operating Temperature
18 °C - 30 °C (65 °F - 86 °F)
VRC-S Operating Humidity
8 - 80 % (non-condensing)
LCD Screen Included
YES
Condensate Pump integrated
YES, powered via rPDU
Condensate Pump tube length
7.5 m (24 ft)
Certifications
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2,
EN 61000-3-2, EN 61000-3-3, RoHS Compliant (EN 50581)
Split System Condensing Unit:
VRC302KIT
Input
Hardwired L+N+PE
Voltage, Frequency
230 Vac , 50/60 Hz
Full Load Amperage (FLA)
6,5 A
Refrigerant type (pre-charged)
R410A, outdoor unit 900 g (1.98 lb)
Dimensions H, W, D; (Inches)
527 mm, 282 mm, 786 mm ( 20.75", 11.10", 30.94")
Net Weight
44 kg (97 lbs.)
Shipping dimensions H,W,D; (Inches)
750 mm, 480 mm, 970 mm (29.53", 18.90", 38.19")
Shipping Weight
70 kg (154 lbs.)
IP Code
IPX4 (IEC 60529)
Outdoor Temperature Range
-15°C (5°F) to 45°C (113°F)
Noise Level
<55 dB(A)
Certifications
CE Marked, Complies with EN 60335-1; EN 60335-2-40, EN 55014-1, EN 55014-2,
EN 61000-3-2, EN 61000-3-3, RoHS Compliant (EN 50581)
Split System Condensing
Unit:
VRC352KIT
Input Power
Hardwired L+N+PE
Voltage, Frequency
230 Vac , 50/60 Hz
Full Load Amperage (FLA)
6,5 A
Refrigerant type (pre-charged)
R410A, outdoor unit 900 g (1.98 lb)
8 Specifications
56
Vertiv™ VRC-S User Manual
Summary of Contents for VRC-S
Page 1: ...VRC S User Manual...
Page 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...
Page 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...
Page 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...
Page 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...
Page 65: ...Vertiv VRC S User Manual...