Mounting Procedure
1.
Remove the front cover panel from the Mounting Frame by first loosening two captive fasteners. Refer
to
NOTE!
In the next step, the Retrofit Mounting Frame CANNOT be installed in the Power Bay unless all
Rectifiers are first removed from the Mounting Frame. Doing so will defeat the precharge circuit in the
rectifiers and cause arching and pitting on the DC power connector!
2.
Ensure no Rectifiers are present in the Mounting Frame.
3.
Slide the empty Mounting Frame into an open mounting position in the Power Bay.
4.
Using the supplied hardware, secure the Mounting Frame to the Power Bay.
Figure 10:
Removing the Cover Panel from the Mounting Frame
Electrical Connections
All electrical connections to the Mounting Frame are made automatically when the Mounting Frame is installed
in the Power Bay. No additional connections are required.
Install the Rectifiers
Procedure
1.
Place one Rectifier into an unoccupied mounting position in the Mounting Frame without sliding it in
completely.
2.
Click the handle on the Rectifier in order to pop it forward out of the front panel (this will also retract the
latch mechanism located on the underside of the Rectifier). See
3.
Gently push the Rectifier completely into the frame.
Mounting Frame
Front Cover Panel
Captive Fasteners