Vertiv
|
NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)
|
Rev. F
25
OPERATION
Local Indicators
Three indicators are located on the front panel of each rectifier in the V200 Retrofit. The functions of these
indicators are as shown in
for the location and identification of the local indicators.
NOTE!
DC voltage must be present at the V200 Retrofit output terminals, (from battery or an operating
rectifier) for local indicators to illuminate.
Figure 13:
Status Indicators
Table 1:
Local Indicators
Indicator
Normal
State
Fault
State
Fault Cause
Power
(Green)
On
Off
No input voltage.
Internal input fuse open.
Flashing
The Rectifier is being identified by the Controller.
Protection
(Yellow)
Off
On
AC input under/over voltage.
PFC output under/over voltage.
High temperature.
Load sharing imbalance.
Flashing
Rectifier communication failure.
Alarm
(Red)
Off
On
Rectifier output disabled for any reason, including overvoltage
shutdown and internal output fuse open. Rectifier addresses
contradictory.
Flashing
Faulty fan (Rectifier shuts down).
Power
Indicator
(Green)
Protection
Indicator
(Yellow)
Fault
Indicator
(Red)