NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)
|
Rev. F
12
c)
Typical Efficiency versus Output Current: See
Figure 3:
Typical Efficiency
Environmental Ratings
Operating Ambient Temperature Range:
a)
Operational: -40°C to +75°C (-40°F to +167°F)
b)
Start: -30°C to +75°C (-22°F to +167°F)
c)
Specification Compliant Full Output: -20°C to +45°C (-4°F to +113°F)
d)
Reduced Load: +45°C to +75°C (+113°F to +167°F). Refer to
Storage Ambient Temperature Range: -40°C to +75°C (40°F to +167°F).
Humidity: This system is capable of operating in an ambient relative humidity range of 0% to 95%, non-
condensing.
Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
Ventilation Requirements: When equipped with V200 Retrofits, a VPS Power Bay must be mounted so
ventilating openings are not blocked and temperature of the air entering the cabinet does not exceed the
Operating Ambient Temperature Range stated previously.
In addition, the distance from the rear of a VPS Power Bay to a wall or other solid structure must not be less
than 15 inches. This will assure proper air flow through the V200 Retrofits.
Audible Noise: The audible noise at any point one meter from any vertical surface of a Power Bay, with one
V200 Retrofit installed and fans operating, does not exceed the following typical levels. A Sound Level Meter
conforming to ANSI S1.4 was used.
a)
Fan at Low Speed: < 59 dBA
b)
Fan at High Speed: < 67 dBA
84
86
88
90
92
94
96
98
0
20
40
60
80
100
Ef
fie
nc
y (
%
)
Load (% of rated load)