password is not displayed on the computer’s screen while you log on.  You have three attempts to enter 
a valid User name and password.  If both are not entered correctly in three attempts, the browser is 
redirected to a blank page.  You will then need to reenter the IP address and press ENTER to reopen the 
login window. 

 

NOTE!  

User names and passwords are case-sensitive.  By default, the User Name and Password 

combination is “admin” and “654321”, respectively. 

 

2.

 

After entering a valid 

User Name

 and 

Password

 and clicking 

OK

,

 the Web Interface Homepage opens.  

See “WEB Interface Menus” on page 27. 

 

NOTE!  

To prevent unauthorized personnel from accessing the power system with your Access Rights, it 

is recommended that you always close your browser when finished with a session. 

 

 

 

 

WEB Interface Menus 

Refer to “WEB Interface Menus” on page 27. 

 

Summary of Contents for NetSure SCC

Page 1: ...NetSure SCC Controller User Manual UM1M520HNA Revision H Specification Number 1M520HNA Model Number M520H...

Page 2: ...ethods tools and materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corp an...

Page 3: ...ode 10 Rectifier and BBU Module Data Monitoring 10 Alarm Detection and Reporting 10 Alarm Logs 10 Specifications 11 Operation 12 SNMP Access 12 SCC Controller Interaction with the RMS 12 Local Indicat...

Page 4: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 4 Replacement Procedures 32 SCC Controller Replacement 32 Troubleshooting 34...

Page 5: ...d ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts...

Page 6: ...ngs and other metal objects c Prior to contacting any uninsulated surface or termination use a voltmeter to verify that no voltage or the expected voltage is present Check for voltage with both AC and...

Page 7: ...is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Han...

Page 8: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 8 This page is intentionally blank...

Page 9: ...the SCC Controller Imminent Power Failure Notification The imminent power fail signal triggers 1 ms before the DC bus collapses It triggers when the combination of rectifiers and batteries on the bus...

Page 10: ...irements are cycled through the group of rectifiers controlled by this feature to provide uniform operating times for each rectifier Rectifier and BBU Module Data Monitoring The SCC Controller monitor...

Page 11: ...185 F Humidity Capable of operating in an ambient relative humidity range of 5 to 95 non condensing Altitude The SCC Controller is capable of operating in an altitude range of 200 feet to 10 000 feet...

Page 12: ...ing an SNMP interface NOTE The rectifier and BBU modules will continue to operate if the SCC Controller fails The rectifier and BBU modules will work if the system is powered up without an SCC Control...

Page 13: ...System DC Output Voltage mV average of non zero values reported by all rectifier and BBU units Get System DC Output Current A average of non zero values reported by all rectifier and BBU units Get DC...

Page 14: ...te Get Set configSystemTimeEx syntax DateAndTime Get Set configTrapTimeFormat Advanced Data SCC Controller to from the RMS Table 6 Detailed Rectifier Data for Each Rectifier Get Set Field Get Set Rect...

Page 15: ...Get Running Time hours Get Fan Status ok failed Get Rated Battery Output Power 90 Seconds W Get Product Model Number Get Serial Number Get Remaining Available Capacity Get Estimate Time to Fully Char...

Page 16: ...date time field One set uses a human readable date time format as a text string the second set uses the DateAndTime format Table 8 Alarms Traps AC Mains Failure AC Mains Failure Ended Rectifier Failu...

Page 17: ...of expected BBUs when the configuration complete flag is set Battery Failure Ended Sent when the failure condition clears EPO Signal Received Sent when the EPO signal is received See EPO Emergency Pow...

Page 18: ...r the rectifier battery with the alarm if applicable Table 11 Historical Alarms Description Index The alarm index number StartTime The date time that the alarm triggered as a string StartTimeEx The da...

Page 19: ...Local Indicators Locations Table 12 SCC Controller Local Indicators Indicator Normal State Fault State Fault Cause Status Green On Off No input voltage to the SCC Controller Internal hardware problem...

Page 20: ...ation It can also set batteryLearningModeStart N to 0 to command the BBU to skip this learning mode request If the BBU starts calibration the SCC will send an SNMP trap to indicate that the BBU is not...

Page 21: ...e Controller Directly to your Computer An Ethernet port is provided in the system This port supports Dynamic Host Configuration Protocol DHCP function Connect your computer to the Ethernet port after...

Page 22: ...ettings to take effect Follow any instruction you see on the screen Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet Network if required NOTE This procedure ne...

Page 23: ...cedure Internet Explorer version 5 5 or newer is required It is best to view the WEB Interface at 1280 x 1024 resolution In newer versions of Internet Explorer you may need to turn Compatibility View...

Page 24: ...ress ENTER to reopen the login window NOTE User names and passwords are case sensitive By default the User Name and Password combination is admin and 654321 respectively 2 After entering a valid User...

Page 25: ...label The date code must be 17 10 or later for BBUs that have compatible firmware The date code must be 15 09 or later for BBUs that can have their firmware upgraded 2 Place BBU modules in a 12 V mod...

Page 26: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 26 Figure 2 BBU Date Code Label Date Code Label Sample Serial Number with Date Code 15 Represents the Year 07 Represents the Month...

Page 27: ...e 3 Web Interface Homepage Setting Static IP SNMP Community Strings and DHCP Communications Parameters From the Homepage you can set Static IP SNMP Community Strings and DHCP communications parameters...

Page 28: ...e file into the controller Press the Back to the Homepage button Downloading Firmware into the SCC Controller Press the GO TO FIRMWARE DOWNLOAD MODE button Select OK The following window opens Figure...

Page 29: ...e Alarms Log Webpage From the Homepage you can access the Active Alarms page The Active Alarms page lists any active alarm recorded by the SCC Controller The Active Alarms page refreshes approximately...

Page 30: ...roller User Manual UM1M520HNA Rev H 30 Alarm History Log Webpage From the Homepage you can access the Alarm History page Alarm events are recorded on the Alarm History page The alarm history log can a...

Page 31: ...ng slot without sliding it in completely 3 Loosen the captive fastener on the SCC Controller s latch mechanism Pull the latch mechanism to pivot it out of the SCC Controller s front panel this also re...

Page 32: ...to the Configuration Label on the side of the replacement SCC Controller for the Configuration Part Number 2 Performing this procedure may activate alarms Notify the appropriate personnel to disregard...

Page 33: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 33 12 Notify appropriate personnel that this procedure is finished and to act upon any future alarms associated with this system...

Page 34: ...n Power is on and SCC is running No action required Status Indicator Green Off No input voltage Make sure there is input voltage Internal hardware problem Replace the SCC Controller Warning Indicator...

Page 35: ...Vertiv NetSure SCC Controller User Manual UM1M520HNA Rev H 35 This page is intentionally blank...

Page 36: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1M520HNA RH 10 19...

Reviews: