Vertiv
|
NetSure™ SCC Controller User Manual (UM1M520HNA)
|
Rev. H
31
INSTALLING THE SCC CONTROLLER
WARNING!
To prevent damage to the latching mechanism, ensure the latch mechanism is in the open
position when installing or removing an SCC Controller. NEVER hold the latch mechanism in the closed
position when installing an SCC Controller into a module mounting assembly.
Procedure
1.
Unpack the SCC Controller.
2.
Place the SCC Controller into its mounting slot without sliding it in completely.
3.
Loosen the captive fastener on the SCC Controller’s latch mechanism. Pull the latch mechanism to pivot
it out of the SCC Controller’s front panel (this also retracts the latch mechanism). See
4.
Push the SCC Controller completely into the module mounting assembly.
5.
Push the latch mechanism into the front panel of the SCC Controller. Tighten the captive fastener on
the latch mechanism. This locks the SCC Controller securely to the module mounting assembly.
Figure 5:
SCC Controller Latch Mechanism
Latch mechanism
must be open when
installing or removing
module.
Latch Mechanism
Captive Fastener