Typical Input Data (1R483200): 60 Hz input.
a)
System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 55 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.62
127
69
0.542
--
235.25
25
4.13
856
842
0.988
88.9
319.31
50
7.92
1644
1639
0.997
91.0
479.51
75
11.87
2457
2453
0.998
91.6
701.88
100
16.02
3298
3297
0.998
90.9
1020.09
110
17.28
3561
3558
0.998
90.5
1156.27
120
16.88
3478
3477
0.998
89.9
1208.42
240
0
0.68
163
66
0.612
--
225.31
25
3.65
865
846
0.977
88.7
325.42
50
6.89
1648
1633
0.994
91.9
453.62
75
10.23
2445
2441
0.998
92.1
654.78
100
13.68
3269
3265
0.998
91.8
917.81
110
14.84
3538
3534
0.998
91.3
1050.24
120
14.46
3455
3454
0.998
90.5
1118.21
b)
Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input Voltage
Input Voltage
Input Current (Amperes)
208/240
176
20.42