Vertiv
|
NetSure Rectifier Module User Manual (UM1R483500e)
|
Rev. R
16
•
Typical Input Data (1R483200e): 60 Hz input.
a)
System output is initially adjusted to 54.48 VDC as measured at the system sense points at 50 % of
full load and nominal input. “Percent of Full Load” refers to percent of 55 amperes.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208Vac
(60Hz)
0
0.397
82.6
9
0.111
--
30.72
25
3.7451
779.7
773.8
0.992
95.49
119.04
50
7.4189
1543.9
1540.7
0.998
95.86
217.91
75
11.2183
2325.1
2323.2
0.999
95.23
378.51
100
15.0624
3118.6
3118.1
0.999
94.38
597.58
110
16.551
3418.3
3417.9
0.999
93.93
707.78
120
16.5356
3419
3418.3
0.999
93.91
710.44
240Vac
(60Hz)
0
0.4651
111.8
8.8
0.804
--
30.03
25
3.2515
780.2
772.1
0.990
95.74
112.17
50
6.4286
1545.1
1536.3
0.994
96.14
202.43
75
9.6608
2318.1
2313.3
0.998
95.65
343.73
100
12.963
3103.8
3100.5
0.999
94.92
537.14
110
14.2095
3399.5
3397.2
0.999
94.50
637.95
120
14.2234
3402.7
3399.9
0.999
94.50
638.09
b)
Maximum Input Current: at 100% of full load with output adjusted to 58 VDC as measured at the
shelf output terminals.
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
19.30