Enclosure G - Ultrasonic Humidifier
G - 2
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
Fig. 2 - Ultrasonic humidifier module in the raised floor, frontal and lateral views
Supply Water.
•
Supply fully demineralized water with conductivity<5 μS/cm. If demineralized water is not available, provided mineralizer (not
supplied);
•
Water pressure from 50 kPa to 500 kPa;
•
Water temperature from 8° C to 40° C;
•
Dust or dirt must not get into the water lines;
Refer to HSU08RM000 manual for details.
Drain Water.
•
The drain water contains the same substances dissolved in the supply water, however in larger quantities;
•
It is not toxic and can be drained into the sewerage system, category 3, EN 1717;
•
Dispose the drain hose into an ordinary drainage network (the drainage network should have a siphon).
Refer to HSU08RM000 manual for details.
G. 2.1 - Infrared humidifier components
1.
Humidifier
2. Fan case
3. Mist guide cover
4. Fan
5. Metal plug
6. Cable
7. Metal plug
8. Cable
9. Water drain
10.
Safety overflow
11. Mist guide pipe
12. Ring and nut
13.
Humidifier drain pan
14.
Air filter
15. Water supply connection
16.
Check valve (to be provided by the Customer)
17. Damper
18.
Humidifier drain pan water drain
Fig. 3 - The Ultrasonic humidifier and its components