3
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
1.3 - Liebert MC™ EconoPhase Version
The Liebert
®
MC air-cooled microchannel condenser is a low-
profile, direct-drive propeller fan-type air-cooled unit suitable for
mounting outdoors. It provides heat rejection for either one or two
separate refrigeration circuits, matches the heat rejection capacity
corresponding with the outdoor ambient temperature and with each
corresponding compressor heat rejection requirements.
Constructed with an aluminum cabinet, galvanized steel frame
and microchannel coil, the unit is quiet and corrosion resistant.
The condenser is quickly and easily installed because all internal
wiring is completed at the factory with only electrical connections
and communications connections to be made at the job site. All
electrical connections and controls are enclosed in an integral
weatherproof section of the condenser.
The
Liebert
®
EconoPhase
pumped refrigerant system will always
use the premium version condenser.
In EconoPhase operation, the premium control board uses
inputs from the indoor unit, condenser refrigerant temperatures
and ambient temperatures to modulate the EC fan motor speed
from 0 to 100% RPM, maintaining the refrigerant temperature
setpoint. The control system provides temperature control for
outdoor ambient as low as -35°C in pumped refrigerant
Liebert
®
EconoPhase
operation.
1.4 - Liebert
®
EconoPhase Pump Refrigerant Module
The
Liebert
®
EconoPhase
is an option for a Liebert
®
PDX
EconoPhase Version air-cooled system. The
Liebert
®
EconoPhase
allows an air-cooled direct expansion system to switch from vapor
compression operation to pumped refrigerant operation when
the outdoor temperature is low enough to provide the required
temperature difference between the inside air and the outside air.
Fig. 2 - Liebert EconoPhase module
1.5 Standard Air-Cooled System vs. Liebert
®
PDX
EconoPhase System
There are differences between the standard air-cooled system and
a system designed with the
Liebert
®
EconoPhase
. The user must
be aware of these differences to achieve the best operation. This
section summarizes the differences; more detailed explanations
are found throughout this manual and the manual of
Liebert
®
EconoPhase
Pump Refrigerant Module.
•
Liebert EconoPhase
Operation - Liebert
®
EconoPhase
operation is possible when the outdoor temperature is low
enough to provide the required temperature difference
between the indoor air and the outside air. This mode turns the
compressors Off and turns the
Liebert
®
EconoPhase
pumps
On.
•
Refrigerant Pumping
- During Liebert
®
EconoPhase
operation, the refrigerant is pumped around the air-cooled
loop instead of going through the vapor compression cycle.
System pressures will vary significantly depending on whether
the system is operating in standard aircooled mode or in
Liebert
®
EconoPhase operation.
•
Energy Savings
- The coefficient of performance of the
system increases significantly during the EconoPhase
operation which results in significant energy savings for the
user.
•
EEV
- The system uses an electronic expansion valve during
both direct expansion and EconoPhase operation. The EEV
results in energy savings and helps the pump maintain proper
differential during EconoPhase operation.
•
Piping
- The condenser piping is larger than what is typically
specified for Liebert
®
air-cooled Precision Cooling systems.
The pipe sizing still allows oil return to the compressor
and also allows for efficient operation in both modes of
operation. All field piped lines must be insulated because the
fluid temperatures can be well below the dew point during
EconoPhase operation. All outdoor insulation must be UV
rated and rated for outdoor use.
•
Unit/Module Communications
- A CANbus connection links
the Liebert PDX and the air-cooled condenser to achieve the
most efficient operation as well as the condenser and the
Liebert
®
EconoPhase
module.
1.6 - Operating Modes
Each circuit on a system combining a
Liebert
®
EconoPhase
,
Liebert DSE and Liebert MC has six distinct operating modes:
•
Idling with compressor and pumps Off
•
Startup
•
Compressor operation
•
Compressor-to-pump changeover
•
Pump operation
•
Pump-to-compressor changeover
A circuit will run most of the time in either compressor or pump
operation mode. These modes both efficiently remove heat from
the conditioned space and reject it via the air-cooled condenser.
The flow paths during each mode of operation are detailed in
Figures 3 and 4.
A couple of differences to note between Compressor Mode and
Liebert
®
EconoPhase
operation:
• The unit does not dehumidify in
Liebert
®
EconoPhase
operation.
If dehumidification is desired,
Liebert
®
EconoPhase
operation
must be disabled.
• Bubbles may be seen in the site glass in the indoor unit when
the system is in
Liebert
®
EconoPhase
operation. This does not
necessarily mean the system is low on charge.