Enclosure F - Infrared Humidifier
F - 1
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
F. 1 - Infrared Humidifier
The infrared humidifier design consists of quartz lamps mounted above a stainless steel water reservoir. The lamps never come in contact
with the water. When humidification of room air is required, infrared rays generate water vapor-without impurities or odor, within seconds.
In order to obtain optimum performance from the humidifier it is advisable to read this manual carefully.
Tab. 1 - Infrared Humidifier specifications
F. 2 - Installation
The infrared humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the
supply water and drain water.
Supply Water.
•
Maximum water pressure 200 kPa
•
Size humidifier supply line for 3.8 l/min, with a minimum water pressure of 138 kPa
•
Do not supply de-ionized water to the humidifier
Drain Water.
•
This contains the same substances dissolved in the supply water, however in larger quantities;
•
It may reach a temperature of 100 ° C;
•
It is not toxic and can be drained into the sewerage system, category 3, EN 1717.
•
Dispose the drain hose into an ordinary drainage network. The drainage network should have a siphon and must be able to withstand
temperatures up to 100° C
UNIT MODEL
PAN
MAIN POWER SUPPLIES
(V ± 10%)
NOMINAL CAPACITY
[kg/h]
ABSORBED CURRENT
[A]
POWER INPUT
[kW]
PX082...165 Stainless steel
400V / 3ph / 50Hz
10
13.9
9.6
F. 2.1 - Infrared humidifier components
1.
humidifier pan
2.
humidifier standpipe
3.
solenoid valve flow regulation
4.
float switch
5. junction block
6. discharge connection
7. supply line
8. manual reset thermostat
9. infrared bulbs
Fig. 1 - The infrared humidifier and its components
Summary of Contents for Liebert PDX
Page 2: ...Liebert PDX EconoPhase Version UM 265133 29 08 2019...
Page 55: ......