225-600kVA Installation Manual | Rev. 8 | 07/2017
39
Notes on Tables
1.
Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal
input current and maximum battery recharge current (considered non-continuous). Continuous and non-continuous
current are defined in NEC 100.
2.
For breaker coordination while the module is overloaded, see the current-versus-time values on the overload curves.
3.
Nominal battery voltage is shown at 2.0 volts/cell.
4.
Maximum Battery current at End of Discharge level of 1.65 volts per cell.
5.
External DC Circuit Overcurrent Protective Device—Caution: To reduce the risk of fire, connect only to a circuit with the
maximum branch circuit overcurrent protection recommended in
Table 13
in accordance with the National Electric Code,
ANSI/NFPA 70.
Table 10
Current ratings—bypass
UPS Rating
kVA/kW
Voltage, VAC
Nominal Current
225
480
271
250
480
301
300
480
361
400
480
481
500
480
601
600
480
722
Table 11
Current ratings—output
UPS Rating
kVA/kW
Voltage, VAC
Nominal Current
225
480
271
250
480
301
300
480
361
400
480
481
500
480
601
600
480
722
Table 12
Current ratings—battery
UPS Rating
kVA/kW
Nominal VDC
Maximum
Battery Current
225
480
600
250
480
667
300
480
800
400
480
1068
500
480
1335
600
480
1600
Table 13
Recommended DC circuit breaker rating
UPS Rating
kVA/kW
Circuit Breaker
Rating, A
225
600
250
700
300
800
400
1200
500
1600
600
1600