Vertiv
™
|
Liebert
®
NX
™
225-600kVA Installation Manual | Rev. 8 | 07/2017
12
2.4
C
ONTROL
C
ABLE
AND
C
OMMUNICATION
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system
(external battery circuit breaker), communicate with a personal computer or provide alarm signaling to external
devices, or for Remote Emergency Power Off (REPO). Refer to
Figures 9
and
15
.
The Liebert NX is equipped with the following interfaces:
•
XS3 - Slot for Liebert IntelliSlot
™
or ManageUPS
™
communication card
•
XS6 - Slot for LIFE
™
Services modem
•
X3 - Reserved
•
X6 - Serial interface for external LIFE Services
•
XT1/2 - Not Used
•
X9 - Reserved
•
XT3/8 - 4-pole screw connector for REPO Input and REPO Status
•
XT4 - Reserved
•
TB1 - 16-pole screw connector for input contacts
•
TB2 - 16-pole screw connector for output contacts
•
X19A/B - 2x15-pole connectors for parallel UPS connection
•
X20 - RJ-45 interface for synchronization with external signal
•
XT1 - Not Used
•
TB3 - Battery Interface and Key Status
•
TB4 - SKRU Enable
2.4.1
Slot for Liebert IntelliSlot
™
or ManageUPS
™
Communication Cards—XS3
This slot is the interface for the Liebert network communication cards. This adapter provides an independent
external network interface for communication with network monitoring and building management systems.
Units built since June 2016 are equipped with either the Liebert IntelliSlot system or the ManageUPS system.
Previous units included a factory-installed ManageUPS system, which provided connectivity to SNMP and
Modbus.
The Liebert IntelliSlot platform includes the Liebert IS-UNITY-DP
™
and Liebert IS-485 EXI
™
cards. The platform
communicates with Vertiv software tools and services, including Trellis
®
, Liebert SiteScan
®
Web and Liebert
Nform
®
.
The Liebert IS-UNITY-DP supports up to two third-party protocols along with HTTP/S (Web), Vertiv Protocol,
SMTP and SMS.
Third-party protocols available on the Liebert IS-UNITY-DP card are:
•
BACnet IP—BACnet over Internet Protocol
•
BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over an RS-485 serial network
(also known as BACnet MSTP RS-485)
•
Modbus RTU
•
Modbus TCP
•
SNMP versions 1, 2c and 3
The Liebert IS-485 EXI Card connects to a Liebert SiteLink-E
™
, allowing Liebert SiteScan Web 4.0 monitoring
and control.
NOTE
No more than two protocols may be enabled on one card.
Only one version of BACnet may be selected, either BACnet IP or BACnet MSTP.
Only one version of Modbus may be selected, either Modbus TCP or Modbus RTU.
Only one of the protocols can use the 485 port; choosing two 485 protocols will cause conflicts.