5 STARTUP PROCEDURE
CAUTION: This UPS must be installed by properly trained and qualified personnel and wired in
accordance with local, national and regional electrical codes.
CAUTION: The utility input supply to the Liebert MicroPOD must be protected by a branch
rated circuit breaker. The UPS output must also be protected with a circuit breaker connected
to the load, rated to carry the input current and be capable of breaking the maximum expected
short circuit current of this branch circuit. The breaker is to be mounted within 6 feet (1.8m) of
the Liebert MicroPOD and be readily accessible to the operator. Refer to on the facing page for
breaker specifications.
5.1 Electrical Connections
Refer to local, regional and national electrical codes to determine the cable sizes and distribution methods
used during installation. on the facing page details the standard current ratings.
5.2 Pluggable Connections
1.
Make sure the Liebert Micro POD rotary switch is in the UTILITY position. Plug the Liebert
MicroPOD input cord (labeled UTILITY) into the utility outlet (wall receptacle).
WARNING! The Liebert MicroPOD is now electrically live. The Utility lamp (amber) should be
illuminated.
2. Plug the UPS input cord into the receptacle on top of the Liebert MicroPOD (labeled:
CONNECT UPS LINE CORD HERE).
WARNING! The UPS system is now electrically live.
3. Connect the Liebert MicroPOD UPS output cord (labeled: UPS) to the output of the UPS
system.
4. Plug in all loads to the output distribution receptacles, distributing them evenly on the Liebert
MicroPOD. The Liebert MicroPOD is powering the equipment in Utility mode.
5. Turn ON the loads following the manufacturer’s instructions; ensure all are operating
according to specification.
6. Start the UPS according to its user manual.
7. Verify that the UPS lamp (green) on the Liebert MicroPOD is illuminated. If so, transfer the
rotary switch from UTILITY to UPS. The load is now being supplied with conditioned power
through the UPS.
8. Before any operation or procedure, always verify that both the UPS lamp (green) and the Utility
lamp (amber) are illuminated before changing the rotary switch.
Vertiv
| Liebert® MicroPOD ™ Installer/User Guide |
12
Summary of Contents for Liebert MicroPOD
Page 1: ...Liebert MicroPOD 120V Installer User Guide...
Page 8: ...Figure 2 3 Liebert MicroPOD connections Vertiv Liebert MicroPOD Installer User Guide 8...
Page 22: ...Vertiv Liebert MicroPOD Installer User Guide 22...
Page 24: ...Vertiv Liebert MicroPOD Installer User Guide 24 This page intentionally left blank...
Page 25: ......