Load
Internal Battery Only
Number of External Battery Cabinets
%
VA
W
1
2
3
4
5
6
7
8
10
200
200
89
181
273
365
456.5
548.5
640.5
732.5
824.5
20
400
400
49
101
153.5
205.5
257.5
309.5
361.5
413.5
465.5
30
600
600
36
74.5
113.5
152
190.5
229.5
268
307
345.5
40
800
8000
26.5
56
85
114.5
144
173
202.5
232
261.5
50
1000
1000
21
44.5
68
91.5
115.5
139
162.5
186
210
60
1200
1200
17
36.5
56.5
76
96
116
135.5
155.5
175
70
1400
1400
14
31
48
65
82
99
116
133
150
80
1600
1600
12
27
42
57
71.5
86.5
101.5
116.5
131.5
90
1800
1800
10.5
23.5
36.5
49.5
63
76
89
102
115.5
100
2000
2000
9
21
32.5
44.5
56.5
68
80
92
103.5
Table 9.6 Battery Run Time in Minutes, GXT5LI-2000IRT2UXL
Load
Internal Battery Only
Number of External Battery Cabinets
%
VA
W
1
2
3
4
5
6
7
8
10
300
270
70.5
144
217
290.5
364
437
510.5
584
657.5
20
600
540
37.5
78
118.5
159
199.5
240.5
281
321.5
362
30
900
810
25
53
81.5
109.5
137.5
165.5
193.5
221.5
249.5
40
1200
1080
18.5
39.5
60.5
82
103
124.5
145.5
166.5
188
50
1500
1350
14
31
48
65.5
82.5
99.5
116.5
133.5
150.5
60
1800
1620
12
26.5
41.5
56
71
85.5
100
115
129.5
70
2100
1890
10
22.5
35
47.5
60.5
73
85.5
98.5
111
80
2400
2160
8.5
19.5
30.5
41.5
52.5
63.5
75
86
97
90
2700
2430
7
17
27
36.5
46.5
56.5
66
76
86
100
3000
2700
6.5
15
24
32.5
41.5
50.5
59.5
68.5
77
Table 9.7 Battery Run Time in Minutes, GXT5LI-3000IRT2UXL
8 Specifications
60
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide