Model
GXT5LI-1000IRT2UXL
GXT5LI-1500IRT2UXL
GXT5LI-2000IRT2UXL
GXT5LI-3000IRT2UXL
Agency
CE, TUV, Energy Star
Safety
IEC 62040-1:2008+A1 2013
IEC62619 Edition1.0 (for battery pack and cell)
UL1973&UL1642 (for battery pack and cell)
EMC
Emission (Low limits – Conducted and radiated):
IEC/EN/AS 62040-2 2nd Ed (Cat2 – Table 1)
CISPR22 Class A (RFI)
IEC 61000-3-2,IEC 61000-3-12 (Harmonics)
Immunity (High commercial and light industry immunity levels for enclosure, power, signal and control ports):
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6) for IEC/EN/AS:
61000-4-2 Electrostatic discharge
61000-4-3 Radiated E-RFI fields
61000-4-4 Fast E transients
61000-4-5 Surges/Lightning
61000-4-6 Conducted RFI
Transportation
ISTA 2A for individually packaged
ISTA 3E for palletized units
UN3480
Surge Immunity
ANSI C62.41 Category B
IEC 61000-4-5
RFI/EMI
CISPR22 Class A (RFI)
Table 9.2 UPS Certification
Model
VEBCLI-48VRT1U
Used With UPS Model
GXT5LI-1000/1500/2000/3000IRT2UXL
Dimensions, W×D×H, inches (mm)
Unit
16.9 x 17.5 x 1.7 (1U) (430 x 446 x 42.5)
Shipping
23.6 x 31.5 x 11.7 (600 x 800 x 297)
Weight, lb.(kg)
Unit
21.8 (9.9)
Shipping
56.2 (25.5)
Battery
Type
Lithium-ion LiFePO4
Configuration x V x Ah
3P16S x 48 V x 9 Ah
Backup time
See
Electrical Protection
Breaker size
80 A
Environmental Requirements
Operating Temperature, °F (°C)
32-122 ºF (0-50 ºC)
Table 9.3 External Battery Specifications
8 Specifications
57
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide