8.1 Battery Run Times
NOTE: Run times in this table are approximate. They are based on new, fully charged batteries at 77°F (25°C), with
fully resistive loads. Run times can vary ±5% due to manufacturing variances.
Load
Internal Battery Only
Number of External Battery Cabinets
%
VA
W
1
2
3
4
5
6
7
8
10
100
100
107
269.5
435
600
765
930
1095.5
1260.5
1425.5
20
200
200
62
154.5
249.5
345
440
535.5
630.5
726
821
30
300
300
42
106.5
174
241.5
308.5
376
443.5
510.5
578
40
400
400
31.5
80
131.5
183
234.5
286
337.5
389
440.5
50
500
500
26.5
68
112
156
200
244.5
288.5
332.5
376.5
60
600
600
22
56
93
130
167.5
204.5
241.5
278.5
315.5
70
700
700
18.5
48
79.5
111.5
143.5
175.5
207.5
239.5
271.5
80
800
800
16
41.5
69.5
97.5
125.5
153.5
181.5
209.5
238
90
900
900
13.5
36
60.5
85.5
110
135
159.5
184.5
209
100
1000
1000
12
32
54
76.5
99
121
143.5
166
188
Table 9.4 Battery Run Time in Minutes, GXT5LI-1000IRT2UXL
Load
Internal Battery Only
Number of External Battery Cabinets
%
VA
W
1
2
3
4
5
6
7
8
10
150
150
104.5
212
319.5
427
534
641.5
749
856.5
964
20
300
300
63.5
130
196.5
263.5
330
396.5
463
529.5
596
30
450
450
44
91.5
138.5
185.5
232.5
280
327
374
421
40
600
600
34
71
108
145.5
182.5
219.5
256.5
293.5
330.5
50
750
750
27
57
86.5
116.5
146.5
176.5
206.5
236
266
60
900
900
22
47
72
97.5
122.5
147.5
172.5
197.5
222.5
70
1050
1050
18
39
60
81.5
102.5
123.5
144.5
165.5
186.5
80
1200
1200
15.5
34
52.5
71
89.5
108
126.5
145
163.5
90
1350
1350
14
31
48
65.5
82.5
99.5
116.5
133.5
150.5
100
1500
1500
13
28
43.5
59.5
75
90.5
106
121.5
137
Table 9.5 Battery Run Time in Minutes, GXT5LI-1500IRT2UXL
8 Specifications
59
Proprietary and Confidential ©2022 Vertiv Group Corp.
Vertiv™ Liebert® GXT5 Lithium-Ion UPS Installer/User Guide