Outlet Parameter Options
Apply the same settings as outlet 1 : Available on Outlet2, this will apply the settings for Outlet1 on any other programmable
outlet.
Turn on/off outlet: Turns on or turns off the outlet based on the current state. Provides a confirmation window with Yes/No
options to confirm turning on the outlet.
Reboot outlet: Cycles power to the outlet. This option is only available when the outlet is on.
Turn on delay: Length of time before outlet turns on after UPS startup.
•
0 to 30 min. (default is 0 min.)
Turn off when UPS overload on battery: Sets whether or not to turn off the outlet if the UPS is overloaded while on battery
power. This can be used to disable lower priority equipment in the event of an overload while in battery mode.
•
Yes
•
No (default)
Outlet settings based on discharging time
Threshold of turning off the outlet: Length of time that the outlet is powered after the batteries begin to discharge. Select the
checkbox to enable or disable (default) the option.
•
0 to 30 min. (default is 5 min.)
Turn on when power returns for: Length of time after the mains input power returns before turning on the outlet. Select the
checkbox to enable (default) or disable the option.
•
0 to 30 min. (default is 0 min.)
Outlet settings based on backup time
Threshold of turning off the outlet: When the selected amount of time remains on battery mode, the outlet is turned off. Select
the checkbox to enable or disable (default) the option.
•
0 to 30 min. (default is 5 min.)
Turn on when power returns for: Length of time after the mains input power returns before turning on the outlet. Select the
checkbox to enable or disable (default) the option.
•
0 to 30 min. (default is 0 min.)
Outlet settings based on capacity
Threshold of turning off the outlet: When the selected percentage of capacity remains in battery mode, the outlet turns off.
Select the checkbox to enable or disable (default) the option.
•
20 to 80% (default is 20%)
Turn on when power returns: Length of time after the mains input power returns before turning on the outlet. Select the
checkbox to enable or disable (default) the option.
•
0 to 30 min. (default is 0 min.)