Notes on the Premium-efficiency Control Board
•
J6 is the CANbus termination jumpers. If the condenser is the last device in the CANbus
communication line, the jumper must be placed between Pins 1 and 2 of J6. If the condenser is
not the last device in the CANbus communication line, then the jumper on J6 must be placed
on Pins 2 and 3. CANbus communication errors may occur if the jumpers are not in the correct
positions.
•
A jumper must be present at J2. If a jumper is not present, the control board will not boot
properly during power startup.
8 Maintenance
41
Summary of Contents for Liebert DSE500
Page 1: ...Liebert DSE500 Packaged Solution Thermal Management System Installer User Guide...
Page 8: ...Vertiv Liebert DSE500 Installer User Guide 8 This page intentionally left blank...
Page 12: ...Vertiv Liebert DSE500 Installer User Guide 12 This page intentionally left blank...
Page 16: ...Vertiv Liebert DSE500 Installer User Guide 16 This page intentionally left blank...
Page 24: ...Vertiv Liebert DSE500 Installer User Guide 24 This page intentionally left blank...
Page 26: ...Vertiv Liebert DSE500 Installer User Guide 26 This page intentionally left blank...
Page 50: ...Vertiv Liebert DSE500 Installer User Guide 50 This page intentionally left blank...
Page 52: ...Vertiv Liebert DSE500 Installer User Guide 52 This page intentionally left blank...
Page 54: ...Vertiv Liebert DSE500 Installer User Guide 54 This page intentionally left blank...