Compressors
1. Check oil level
2. Check for oil leaks
3. Check compressor mounts (bushings)
4. Cap tubes (not rubbing)
5. Check/Re-torque wire connections (inside compressor box)
6. Compressor operation (vibration/noise)
7. Check crank-case heater fuses/operation (if equipped)
8. Check for refrigerant leaks
9. Suction pressure
Circuit #1
Circuit #2
10. Discharge Pressure
Circuit #1
Circuit #2
11. Superheat
Circuit #1
Circuit #2
12. Low-pressure switch cut out
Circuit #1
Circuit #2
13. Low pressure cut in
Circuit #1
Circuit #2
14. High pressure cut out
Circuit #1
Circuit #2
15. Amp draw
Circuit #1A
L1
L2
L3
Circuit #1B
L1
L2
L3
Circuit #2A
L1
L2
L3
Circuit #2B
L1
L2
L3
Condenser
1. Coil clean
2. Fans free of debris
3. Fans securely mounted
4. Motor bearings in good condition
5. Check all refrigerant lines for vibration isolation. Support as necessary
6. Check for refrigerant leaks
7. Check surge-protection device (if installed) status-indicator lights
8. Check/Re-torque wire connections
9. Check contactors for pitting (replace if pitted)
10. Verify operation sequence/set points
11. Charge verification:
a. Outdoor Ambient Temperature __________
b. Subcooling __________
c. Indoor-unit Return-air Temperature __________
d. Sight-glass level (if Lee-Temp or pumped refrigerant) _________
12. Motor amp draw
#1
L1
L2
L3
#2 L1
L2
L3
#3 L1
L2
L3
#4 L1
L2
L3
#5 L1
L2
L3
#6 L1
L2
L3
#7 L1
L2
L3
#8 L1
L2
L3
Vertiv | Liebert® DSE500™ Installer/User Guide
48
Summary of Contents for Liebert DSE500
Page 1: ...Liebert DSE500 Packaged Solution Thermal Management System Installer User Guide...
Page 8: ...Vertiv Liebert DSE500 Installer User Guide 8 This page intentionally left blank...
Page 12: ...Vertiv Liebert DSE500 Installer User Guide 12 This page intentionally left blank...
Page 16: ...Vertiv Liebert DSE500 Installer User Guide 16 This page intentionally left blank...
Page 24: ...Vertiv Liebert DSE500 Installer User Guide 24 This page intentionally left blank...
Page 26: ...Vertiv Liebert DSE500 Installer User Guide 26 This page intentionally left blank...
Page 50: ...Vertiv Liebert DSE500 Installer User Guide 50 This page intentionally left blank...
Page 52: ...Vertiv Liebert DSE500 Installer User Guide 52 This page intentionally left blank...
Page 54: ...Vertiv Liebert DSE500 Installer User Guide 54 This page intentionally left blank...