Vertiv
|
eSure™ Power Extend Converter Installation and User Manual (UM565050)
|
Rev. D
17
undershoot more than 5% of the regulated output level. The
output voltage returns and stays within the ±1% regulation band
within 4 milliseconds. (Telcordia GR-947-CORE.)
c)
Overshoot/Undershoot: 1.0% maximum output voltage overshoot
at turn-on (high voltage shutdown does not activate). No
voltage undershoots at turn-off.
d)
Output Voltage Accuracy: ±0.15 V (at -58 VDC and 50% load
and nominal input voltage [52V to 56.5V]).