Vertiv | VE Series Rack | User Manual
Installation Instructions
•
The EIA rails are in firm contact with the crossbeam through spray protection, the top cover is protected
by spraying and the grounding shrapnel is in firm contact with the crossbeam, and the bottom panel and
frames are firmly connected by M5 self-tapping screws and paint-breaking gaskets, so that the EIA rail,
top cover, and bottom panel need not use a grounding cable.
•
When connecting the side panel with the crossbeam, the left and right sides of the panel must be
connected with the crossbeam grounding wire, the grounding position is identical.
3.8.
Rack Main Grounding Points
The rack is provided with both front and rear main grounding points inside the lower width beam on the front and rear
frames, three main grounding points are present at both front and rear ends respectively, and the rack is equipped with
one M6 main grounding screw, as shown in
Figure 3-20
.
B
B
A
A
A-A
B-B
Main grounding
point of back
Rear
door
Front
door
Main grounding
point of front
Main grounding point
Figure 3-20 Rack Main Grounding Points
•
Rack needs to be securely connected and guided by grounding wires, from the main grounding points to
the external grounding position, otherwise there may be a risk of electric shock.