background image

21

3

3-Wire Conduit Installation 

(See Figure 3.5)

1.  Remove the 

Terminal Block Access Plate

 on the back of the 

range by unscrewing the 4 fixing 

Screws

 (Figure 3.4).

2.  Check the correct positioning of the 

Conduit Bracket

 as per 

figure 3.5.

3.  Feed 1/2” (1.3 cm) trade size 

Conduit

 through the hole in the 

Conduit Bracket

  and  secure  to  the 

Conduit Bracket

  with  a 

Conduit Clamp

.

4.  Plug the terminal holes of conductors.

 

The 

Neutral or Ground Wire

 must be connected to the neutral 

terminal located in the center of 

Terminal Block

.

 

The 

Power Wires

 must be connected to the outside terminals.

5.  Plug washers and tighten nuts securely.

 

 Do not remove 

Ground strap

.

6.  Reassemble the 

Terminal Block Access Plate

 on the back of 

the range by screwing the 4 fixing 

Screws

 (Figure 3.4).

4-Wire Conduit Installation 

(See Figure 3.6)

1.  Remove the 

Terminal Block Access Plate

 on the back of the 

range by unscrewing the 4 fixing 

Screws

 (Figure 3.4).

2.  Check the correct positioning of the 

Conduit Bracket

 as per 

figure 3.6.

3.  Feed 1/2” (1.3 cm) trade size 

Conduit

 through the hole in the 

Conduit Bracket

  and  secure  to  the 

Conduit Bracket

  with  a 

Conduit Clamp

.

4.  Remove the 3 wire terminal nuts and washers from the 

Termi-

nal Block

.

5.  Remove the 

Ground Strap

 from the frame of range and termi-

nal by removing its screw and cutting it as shown in Figure 3.6.

6.  Plug the terminal holes of conductors.

 

The 

Neutral Wire

  must  be  connected  to  the  neutral  terminal 

located in the center of 

Terminal Block

; the 

Power Wires

 must 

be connected to the outside terminals; the 

Ground Wire

 must 

be attached to the frame of range by using the (Ground) identi-

fied     

Grounding Screw

.

7.  Plug washers and tighten nuts securely.
8.  Reassemble the 

Terminal Block Access Plate

 on the back of 

the range by screwing the 4 fixing 

Screws

 (Figure 3.4).

Terminal Block

Ground strap

Neutral Wire

Power Wires

Conduit

Conduit Clamp

B

Power Cord

Bracket

A

: D=1” 9/64 (29 mm)

B

: D=7/8” (22.5 mm)

A

Terminal Block

Cut Ground Strap

Neutral Wire

Power Wires

Conduit

Conduit Clamp

Grounding Wire

Grounding

Screw

B

Power Cord

Bracket

A

: D=1” 9/64 (29 mm)

B

: D=7/8” (22.5 mm)

A

Terminal Block

Access Plate

Screws

Screws

Fig. 3.4

Fig. 3.5

Fig. 3.6

Summary of Contents for VEFSGE 304 SC

Page 1: ...ane Installation Code and or local codes Electrical installation must be in accordance with the current CSA C22 1 Canadian Electrical Codes Part 1 and or local codes INSTALLATION IN MANUFACTURED MOBIL...

Page 2: ...rm the room Doing so may result in carbon monoxide poiso ning and overheating of the appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not u...

Page 3: ...red to publish a list of substances known to the state of Califor nia to cause cancer or reproductive harm and requires businesses to warn customers of potential exposures to such substances WARNING G...

Page 4: ...erty damage Consult a quali fied installer service agent or the gas supplier Screwdriver 2 Wrench T handle wrench Tape measure Pencil Adjustable pliers Adjustable wrench Suitable protective gloves Dri...

Page 5: ...electrical supply to the appliance before ser vicing 11 When removing appliance for cleaning and or service A Shut off gas at main supply B Disconnect AC power supply C Disconnect gas line to the inl...

Page 6: ...r side vertical surfaces above 36 914 mm high There must be a minimum of 11 13 16 300 mm side clearance from the range to such combustible surfaces TO THE LEFT or TO THE RIGHT above the 36 914 mm high...

Page 7: ...he 2 screws A interposing the spacers Screw the central screw B 1 Fig 1 3 GAS AND ELECTRIC CONNECTION Fig 1 2 Dotted line showing the position of the range when installed Area for ELECTRICAL connectio...

Page 8: ...A PROXIMITY TO SIDE CABINETS STANDARD INSTALLATION Fig 1 4b Fig 1 4a OVEN VENT Ref inch mm A 0 0 B 36 914 C 11 13 16 300 D 30 minimum 762 minimum E 18 minimum 457 minimum F 13 maximum 330 maximum G 20...

Page 9: ...ON A A B G E D F C H A A B G E D F C H Fig 1 5b Fig 1 5a OVEN VENT Ref inch mm A 0 0 B 36 914 C 11 13 16 300 D 30 minimum 762 minimum E 18 minimum 457 minimum F 13 maximum 330 maximum G 20 minimum 500...

Page 10: ...ILITY DEVICE FIXING Anti tip stability device Rear left feet of range 3 15 64 82 mm YOU MUST USE STABILITY ANTI TIP BRACKET TO PREVENT UNIT FROM TIPPING ANTI TIP STABILITY DEVICE INSTALLATION INSTRUCT...

Page 11: ...the backguard 2 Remove the pan supports the burner caps and the flame spreaders 3 Unscrew cooktop fixing screws A in figure below 4 Remove the dual burner inner flame spreader B in figure below 5 Remo...

Page 12: ...st be made according to national and local codes This gas supply service line must be the same size or greater than the inlet line of the appliance Sea lant on all pipe joints must be resistant to the...

Page 13: ...Do not over tighten the connector Over tightening may crack regulator STEP 2 Assemble the 1 2 NPT connector pressure regulator group to the extension pipe interposing the gasket supplied The regulato...

Page 14: ...fitting To range 1 2 G cylindrical ISO 228 1 female Extension pipe 1 2 G cylindrical ISO 228 1 male Extension pipe male pipe fitting Gasket Connector 1 2 NPT conical male 1 2 NPT female Pressure regu...

Page 15: ...ated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI 3 5 kP...

Page 16: ...iameters expressed in hundredths of a millimetre are marked on the body of each injector CAUTION Save the orifices removed from the appliance for future use SETTING THE PRESSURE REGULATOR The pressure...

Page 17: ...plate D and screw the no 2 fixing screws C then refit the inner crown flame spreader B and screw the no 3 fixing screws A Refit the flame spreaders the burner caps and the pan supports The burner are...

Page 18: ...til adjustment is correct Outside crown of DUAL burner Light the DUAL burner Set the gas valve to position minimum rate of inner and outer crowns Remove the knob With a thin screwdriver turn the regul...

Page 19: ...ectly to the fused disconnect or circuit breaker box through flexible counduit with copper or aluminium wiring with grounding wire Allow two to three feet of slack in the line so that it can be moved...

Page 20: ...ck the correct positioning of the Power Cord Bracket as per figure 3 3 3 Assemble the strain relief in the hole on Power Cord Bracket 4 Insert the Power Cord through the strain relief and tighten 5 Re...

Page 21: ...as per figure 3 6 3 Feed 1 2 1 3 cm trade size Conduit through the hole in the Conduit Bracket and secure to the Conduit Bracket with a Conduit Clamp 4 Remove the 3 wire terminal nuts and washers from...

Page 22: ...R SAFETY PILOT LAMP CF COOLING FAN OF OVEN FAN DLM DOOR LOCK MOTOR SL U STATUS LOCK UNLOCK LPL LINE PILOT LAMP ST SAFETY THERMOSTAT EL P ELECTRONIC PROGRAMMER SD DOOR STATUS OPEN CLOSED ODL OVEN DOOR...

Page 23: ...23...

Page 24: ...rors in the present booklet The manufacturer reserves the right to make all modifications to its products dee med necessary for manufacture or commercial reasons at any moment and without prior notice...

Reviews: