SB50HB Series Woodburning Fireplace
OuTSIde COMBuSTION aIr preCauTIONS & reCOMMeNdaTIONS
NOTe
:
The use of outside air for combustion is optional unless required by building codes. It
is only necessary to supply outside combustion air to one side of the fireplace. Use the model
AK4 combustion air kit.
&0
/!STARTCOLLAR
Insulation Ring
Insert Shortest Side of the
Tube through the Fireplace
Outer Wrap to Properly
Seal Against Firebox Wall
and Gasket
Longer Length of the Tube
to Outside
Secure Outside air Starting Collar to Fireplace
Figure 28
Step 1:
Secure outside air starting collar to left side of fire-
place with four (4) sheet metal screws provided.
NOTe:
The starting collar extends through the outer fireplace
jacket and will seal against the firebox wall when secured as
indicated.
FP1900
&0
SECUREOUTSIDEDUCT
Step 2:
Secure outside duct to starting
collar with duct clamp or screws
.
Fireplace Outer Wrap
AK4 Combustion Air
Kit (Shortest Toward
Firebox)
AK4 Mounting Plate
Firebox Insulation Seal
FP1901
&0
ABOVEBASEMENT
Firestop
Spacer
Duct Extended
to Avoid Joint
Second Floor
To Outside Wall
FP9
Installation above Basement or
Crawl Space
8’ Max.
FP2230
OA soffit install
1/09
Chimney
Cap
Firestop
CauTION:
Do not
take air from attic
spac or garage.
Inlet Grille
in Soffit
(Overhang)
FP30
Concrete Slab Installation
(Optional Outside Air Runs)