33
10002428
Vermont Castings, Majestic Products DVRT36/ 39/ 43
Auto Path Chart
If the manual switch is
set to REMOTE,
press the mode button
to display AUTO on the
transmitter. Does the
transmitter display the
room and temperature
setting?
If the settings is above
room temperature on
the transmitter, did
the main valve and
fan turn On?
Turn pilotstat knob to
OFF to turn the valve
completely Off.
Auto Path
Move switch from
LOCAL to REMOTE.
Press any key
within 30 seconds.
Yes
Yes
No
No
If the settings is below
room temperature on
the transmitter, did
the main valve and
fan turn Off?
LED Count Service Action
8
Replace valve
7
Confirm stepper motor connection exists
5
Confirm fan connection exists and works
4
Confirm gas type; jumper in place
3
Replace thermopiles
2
Turn fan ON
NOTE: Some keys are not active.