40
Chateau™ Direct Vent Gas Fireplace
20011957
22. Turn on gas supply and operate valve with remote
control as needed to indicate gas pressure. The
manifold pressure for LP should be approximately
10.0” wcp.
CAUTION:
Turn off the valve and gas supply
before removing test port adaptor and replac-
ing plug.
23. After test, remove adaptor and replace plug.
24. Turn on gas supply and check that plugs are tight
and leak free.
25. Follow instructions in Homeowner’s Manual to
re-assemble brick panels, logs, lava rock, volcanic
rock, embers and andirons.
26. Replace glass frame.
27. Conversion complete.
Table 1 DVT38S2 Injector Orifice Size Matrix
Conversion to LP
KiT #
Burner
20012368
Burner
Housing/
Burner
Burner
Input (BTU/hr)
Model
Housing
Part #
Pilot*
Part #
Tube
Part #
Tube
Part #
Min.
Max.
DVT38S2IP
#55
30000333
#54
20000130
#57
20004587
#57
20004587 38,000 56,000
(.052”)
(.055”)
(.043”)
(.043”)
Table 2 Valve Minimum Rate Screw
Model
Drill Size
Part #
DVT38S2IP
No Shank
20012264
Screw
Pilot Flame Adjustment
Typically, the top 3/8” or 1/2” of the pilot flame sensor
should be engulfed in the pilot flame. (Page 32, Fig. 51)
To adjust pilot burner:
1. Locate pilot adjustment screw on the valve next to
the black plastic cap. Refer to Page 34.
2. Adjust pilot screw to provide proper sized flame.
Only a small adjustment should be needed.
NOTE:
Do not rotate screw excessively. Do not adjust
any other screws on the valve.