Chateau™ Direct Vent Gas Fireplace
20011957
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertical through the roof.
•
Only CFM Corporation venting components spe-
cifically approved and labelled for this fireplace
may be used.
•
Venting terminals shall not be recessed into a wall or
siding.
•
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, gar-
den sheds, fences, decks or utility buildings within 24”
(610mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on following
page.