HW2 Protocol Series Installation Guide
Objects Table:
Object Name
Object Identifier
Object Property
Room Temperature
AI 1
Temperature in Room
Room Humidity
AI 2
Humidity in Room
Temperature Setpoint*
AV 1
Setpoint Value for Temperature
Humidity Setpoint*
AV2
Setpoint Value for Humdidity
Touch Disable*
BV2
ACTIVE disables Touch Response
INACTIVE enables Touch Response
Temperature Units*
BV4
ACTIVE displays temperature in Fahrenhiet
INACTIVE displays temperature in Celsius
Occupancy Override
BV5
ACTIVE means room is not occupied
INACTIVE means room is occupied
Screen Timeout*
BV 6
ACTIVE enables Screen Timeout
INACTIVE disables Screen Timeout
Display Humidity*
BV7
ACTIVE displays humidity on Screen
INACTIVE removes humdity from Screen
Display Setpoint*
BV11
ACTIVE displays temperature setpoint on main screen
INACTIVE displays temperature setpoint in upper left
corner and current temperature on main screen
Screen Color Set*
MSV 1
Selection for Screen Color Theme
Fan Speed*
MSV 2
Fan Speed Selection
* Preserved during power outages.
Device Objects Table:
Object Name
Object Identifier
Object Property
Description
Living Space Room Unit XXXXXXX Ven nnn
Object _Identifer (R/W)
Unique value where nnn initially is the
MS/TP address
BACnet Protocol Implementation Conformance Statement
Vendor Name: Veris Industries
Product Name: Living Space Room Unit
Product Model: HW2XXXX
BACnet Protocol Version : 1
BACnet Protocol Revision: 16
Product Description: Environmental Sensor
BACnet Standardized Device Profile (AnnexL):
BACnet Application Specific Controller (B-ASC)
List All BACnet Interoperatvility Building Blocks Supported(Annex K):
DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B
Data Link Layer Options: MS/TP (Clause 9), baud rates, 9600, 19200, 38400, 76800
Device Address Binding: Static Device binding is not supported.
Networking Options: None
Character Sets supported: ISO 10646 (UTF-8)