HW2 Protocol Series Installation Guide

Communications Configuration:

 

See the Product Diagram section for the location of the DIP switch labeled “CONFIG”. The following parameters are 

configurable: 

            - Parity (Modbus only): None, Odd, None1 (one stop bit), Even 

            - Baud rate: 9600, 19200, 38400, 57600 (Modbus), 76800 (BACnet) 

 

 

off

off

on

off

off

on

on

on

None

Odd

None1

Even

9600

19200

38400

57600 (Modbus)
76800 (BACnet)

off

off

on

off

off

on

on

on

Parity

(Modbus Only)

Baud

DIP Switches 5 to 8

are Unused

 

 

Example: No Parity, 19200 Baud 

1

2

3

4

5

6

7

8

off

off

on

off

off

off

off

off

None

19200 Baud

Unused

 

Modbus Point Map

 

Function Codes: 

Function Code

Function

03

Read holding (RW) registers

04

Read input (RO) registers

06

Write single register*

16

Write multiple registers

01

Read coils

05

Write single coil

15

Write multiple coils

* Not supported. 

 

All of these values correspond to BACnet objects with the same name. See the BACnet Conformance Statement for their 

definitions. 

 

Note that an attempt to write to “read only” holding registers will give an error and the entire write command will not be 

executed even if writing to read/write locations were also requested. Exception code 2 is given in this case. “Preserved” means 

the values is maintained through power outages. 

 

32-Bit Input Registers (Read Only): 

Register

Description

1

Temperature reading in IEEE 32-bit floating point

3

Humidity reading in IEEE 32-bit floating point

9

Model (numeric representation of ASCII characters)

42

Serial number (numeric representation of ASCII characters)

Installation (cont.)

Summary of Contents for HW2 Series

Page 1: ...atform for use with BAS controllers designed to accept BACnet and Modbus outputs HW2 Protocol Series sensors are available with three user interface options touchscreen LCD with three buttons and blan...

Page 2: ...point Temperature humidityorfanspeedselectable Timeoutoverride Displaytimeout Lockoutoverride Touchscreen buttonlockout SETPOINTS Temperature Setpoint Scale 0to50 C 32to122 F or10to35 C 50to95 F max a...

Page 3: ...the cover from the base at the bottom of the device 2 Position the sensor base vertically on the wall 1 35 m 4 5 ft above the floor with the UP arrow facing upward Locate away from windows vents and...

Page 4: ...f an address is selected that conflicts with another device neither device will be able to communicate Address the device as any whole number between and including 1 to 127 Note that zero is not a val...

Page 5: ...o Parity 19200 Baud 1 2 3 4 5 6 7 8 off off on off off off off off None 19200 Baud Unused Modbus Point Map Function Codes Function Code Function 03 Read holding RW registers 04 Read input RO registers...

Page 6: ...en Preservedduringpoweroutages BACnet Descriptions Note In the tables below all properties are read only unless otherwise noted Preserved means the value is maintained through power outages Present_Va...

Page 7: ...y Setpoint BV11 ACTIVE displays temperature setpoint on main screen INACTIVE displays temperature setpoint in upper left corner and current temperature on main screen Screen Color Set MSV 1 Selection...

Page 8: ...ius Temperature value Fahrenheit Celsius Temperature setpoint Menu button RH value Menu button RH value 0 C 100 100 20 20 5 C 23 MenuScreen The menu screen opens when pressing the Menu button on the m...

Page 9: ...eherebyacknowledgedtobelongtotheirrespectiveowners HW2 Protocol Series Installation Guide MenuButtonFunctions cont Touchscreen Operation cont Submenu Only Fan Speed Click this icon to access the fan s...

Page 10: ...s Fahrenheit The Menu Advance button cycles between Temperature RH Fan Speed setpoints and Celsius Fahrenheit adjustment screens in order TemperatureSetpointAdjustment RHSetpointAdjustment ChangeValue...

Page 11: ...s above the limit as stipulated in GB T 26572 Z000057 0B Part Name Hazardous Substances Pb Hg Cd Cr VI PBB PBDE Electronic Environment FriendlyUsePeriod EFUP Table FanSpeedSetpointAdjustment ChangingC...

Reviews: