INSTALLATION GUIDE

As an alternative to the table on the previous page, it can be convenient to invert the values for use as divisors, where the  
integer value returned by the Enercept is divided by a number from the table below. In most cases, the divisors are a more  
compact number.

Addr

Units

100A

300/400A

800A

1600A

2400A

40001

kWh

128

32

16

8

4

40002

kWh

1.9531E-3

4.8828E-4

2.4414E-4

1.2207E-4

6.1035E-5

40003

kW

250

62.5

31.25

15.625

7.8125

40004

VAR

250

62.5

31.25

15.625

7.8125

40005

VA

250

62.5

31.25

15.625

7.8125

40006

---

32768

40007

VOLTS

32

40008

VOLTS

64

40009

AMPS

256

64

32

16

8

40010

kW

1000

250

125

62.5

31.25

40011

kW

1000

250

125

62.5

31.25

40012

kW

1000

250

125

62.5

31.25

40013

---

32768

40014

---

32768

40015

---

32768

40016

VOLTS

32

40017

VOLTS

32

40018

VOLTS

32

40019

VOLTS

64

40020

VOLTS

64

40021

VOLTS

64

40022

AMPS

256

64

32

16

8

40023

AMPS

256

64

32

16

8

40024

AMPS

256

64

32

16

8

40025

kW

250

62.5

31.25

15.625

7.8125

40026

kW

250

62.5

31.25

15.625

7.8125

40027

kW

250

62.5

31.25

15.625

7.8125

Summary of Contents for ENERCEPT H8035

Page 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Page 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Page 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Page 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Page 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Page 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Page 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Page 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Page 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Page 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...

Reviews: