background image

H8035/H8036

Z201686-0K 

PAGE 10 

©2010 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

10101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

TROUBLESHOOTING

Problem

Solution

Status LED does not blink

Check fuses and voltage connections. Status 
LED should blink regardless of CTs, Modbus 
connections, and DIP switch setting.

Enercept interferes with 
another device on the Modbus  
network

Set DIP switches to a different Modbus address 
not in use.

Readings seem highly 
inaccurate.

•  Check that each CT is installed on the conductor 

with the corresponding color voltage input 
lead attached. In most cases, incorrect wiring 
will cause the STATUS LED to blink RED (slowly).  
However, a power factor lower than 0.5 could 
cause the LED to blink this way, even if the unit is 
installed properly.

•  It does not matter which side of the CT faces 

towards the load.

•  If current is below 7% of full scale maximum 

for the CT, use a smaller CT or wrap each wire 
through the CT multiple times

•  Check current with an amp-clamp. 

Expected power:  
kW = Volts x Amps x 1.732 x PF / 1000
kW = Horsepower x 0.746
PF is usually 0.7 to 0.95, depending on the load.

Enercept goes offline when 
load is switched off.

Voltage leads must be connected on the Line 
side of the conductor. The Enercept cannot 
communicate on the Modbus network without 
voltage.

Status LED blinks red.

•  If the LED blinks quickly (i.e., about 5 blinks in 

two seconds), then the use a CT with a higher 
amp rating.  

•  If the LED blinks slowly (i.e., about 1 blink in 

two seconds) the CTs are not installed on the 
correct conductors, or the power factor is less 
than 0.5. The Enercept can accurately measure 
these low PFs, but few loads operate normally at 
such a low power factor.

Summary of Contents for ENERCEPT H8035

Page 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Page 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Page 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Page 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Page 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Page 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Page 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Page 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Page 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Page 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...

Reviews: