H8035/H8036

Z201686-0K 

PAGE 4 

©2010 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

10101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

WIRING

Typical 208/480 VAC 3Ø, 3- or 4- Wire Installation

MODBUS RS-485 LINE

ØB

ØA

ØC

Typical 240/120 VAC 1Ø, 3-Wire Installation

120   

Neutral  

120   

MODBUS RS-485 LINE

To additional MODBUS Devices

ØA

ØB

Typical 277 VAC 1Ø, 2-Wire Installation

Neutral

277   

MODBUS RS-485 LINE

To additional MODBUS Devices

ØA

NOTES

1.  DO NOT GROUND THE SHIELD INSIDE THE ELECTRICAL PANEL. All Modbus wires, 

including the shield, should be insulated to prevent accidental contact with high 
voltage conductors.

2.  The Modbus cable should be mechanically secured where it enters the electrical 

panel.

3.  All Modbus devices should be connected together in a daisy-chain fashion. The 

first and last devices in the chain should have a 120Ω terminating resistor between 
(+) and (-).

4.  The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar.

WARNING:  After wiring, remove all scraps of wire or foil 

shield from the electrical panel.  This could be DANGER-

OUS if wire scraps come into contact with high voltage 

wires!

OUTPUT

H8035
kWh, consumption
Reset kWh
kW, demand

H8036
kWh, consumption
kW, real power
VAR, reactive power
VA, apparent power
Power factor
Average real power
Minimum real power
Maximum real power
Voltage, line-to-line
Voltage, line-to-neutral
Amps, average current
kW, real power ØA
kW, real power ØB
kW, real power ØC
Power factor ØA
Power factor ØB
Power factor ØC
Voltage, ØA to ØB
Voltage, ØB to ØC
Voltage, ØAto ØC
Voltage, ØA to Neutral
Voltage, ØB to Neutral
Voltage, ØC to Neutral
Amps, Current ØA
Amps, Current ØB
Amps, Current ØC

Note: The Enercept cannot communicate on the network bus without power. 
Therefore, it is best to connect the voltage leads ahead of switching devices.

5.  For information regarding software setup, see the Modbus protocol specifications 

available at www.veris.com/Modbus/.

6.  Check power reading (these calculations are approximations only).

Expected power:  

kW = Volts x Amps x 1.732 x PF / 1000

kW = Horsepower x 0.746

Summary of Contents for ENERCEPT H8035

Page 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Page 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Page 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Page 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Page 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Page 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Page 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Page 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Page 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Page 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...