Table 6: ZEC510-1 - controller wiring diagram
Number Description
Name on the
Verasys user
interface
Terminal
label
Object name Signal type
1
24 V HOT power transformer
2
24 V COM power transformer
3
Electric heat safeties
n/a
4
Optional. Heating stage command 1
HEATING STAGE
COMMAND 1
OUT1
HTG1-C
24 VAC on/off,
internally sourced
5
Optional. Heating stage command 2
HEATING STAGE
COMMAND 2
OUT2
HTG2-C
24 VAC on/off,
internally sourced
6
Optional. Supply fan command
SUPPLY FAN
COMMAND
OUT3
SF-C
24 VAC on/off,
internally sourced
7
Optional. Supplemental heating stage
command
SUPPLEMENTAL
HEATING STAGE
COMMAND
OUT4
SUPHTG1-C 24 VAC on/off,
externally sourced
8
Optional. Heating stage command 3
HEATING STAGE
COMMAND 3
OUT5
HTG3-C
24 VAC on/off,
externally sourced
9
Pressure ports. No polarity
10
Manual override
n/a
11
Optional. Supply air temperature
sensor TE-631GV-2.
SUPPLY AIR
TEMPERATURE
IN3
SA-T
Nickel 1K RTD
12
Optional. Relay: RIBU1C
13
Occupancy sensor OLS-2100-1. To red
wire occupancy switch
14
Occupancy sensor OLS-2100-1. To
neutral occupancy switch
OCCUPANCY
STATUS
IN2
OCC-S
Dry Contact, Normally
Open
Normally Closed is
configurable
through the interface
15
Optional. Discharge air temperature
sensor TE-631GV-2.
DISCHARGE AIR
TEMPERATURE
IN1
DA-T
Nickel 1K RTD
16
To next device
17
From last device
18
See riser schedule to determine the EOL
device. You must set the EOL switch to
the
ON
position on the EOL device.
n/a
19
Zone temperature sensor
NSB8BTN240-0. The connector is
located on the back of the sensor.
ZONE
TEMPERATURE
SENSOR BUS
ZN-T
20
Optional. Zone CO
2
sensor NS-
BCN7004-0. The connector is located on
the back of the sensor.
ZONE AIR QUALITY
or ZONE CO2
SENSOR BUS
ZN-CO2
Sensor Actuator
(SA) bus
Note:
• Heating or fan contactors are in the VAV box. The VAV controller binary outputs switch the
common. OUT1, OUT2, and OUT3 are 24 V HOT continuously.
• You can average up to five NS sensors. Connect the NS sensors in a daisy-chain
configuration using the addresses in the
section. The fifth
sensor must have the fixed address 199.
• If you install CO
2
Net sensors, in addition to the 24 VAC power for the controller, you must
also supply 24 VAC power to the
HOT
and
COM
terminals.
Verasys ZEC510 VAV Controllers Installation Guide