VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System – User Guide V1.0
48
To clear or enable write a "1", or to disable write a "0".
An xample to reset battery data, g10v01 q00 start 0 stop 0 value 1, would be to issue
an application layer write command of the form:
c5 02 0a 01 00 00 00 01
Point
Description
State
Value
State
Value
0 Battery Data Reset
Write to Enable
0x81
Write to Disabled 0x01
1 Battery LV Disconnect Enable
Write to Clear
0x81
Cleared
0x01
2 Battery Test Enable
Write to Start
0x81
Write to Stop
0x01
3 Battery Start / Stop Test
Write to Start
0x81
Write to Stop
0x01
9.1.3.9.
Events
When Events are generated, they are reported via unsolicited messaging (if
enabled), or queue to the event list for reading when polling for Class 2 data, or
reading Binary events. Event points correspond to Binary Input Points.
Point
Description
State
Value
1 Low Battery Capacity Event
Tripped Event
0x81
2 Low Battery Voltage Event
Tripped Event
0x81
4 Aux IO Channel 1 Event
Tripped Event
0x81
5 Aux IO Channel 2 Digital In
Tripped Event
0x82
9.1.3.10.
9.2. Mod Bus
- expected Q3/2013