VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System – User Guide V1.0
17
7.2. Battery Status Page
7.2.1. Capacity Test Settings Results.
This field displays the time stamp for the last battery capacity test was
performed, the average load current, and the average enclosure temperature
the test was performed at.
7.2.2. Current Status.
This field displays the estimated time to perform the battery capacity test. The
test is terminated when the battery voltage goes below 11 Vdc for a 12 Vdc
system or 22 Vdc for a 24 Vdc system. This is based on the battery capacity
curves for lead acid batteries and the average load current of the system. The
field also displays the minimum run time for the battery capacity test and the
status of the last test performed.