background image

7

3. INSTALLATION 

(

CONT

D

)

3.4 P

LANNING

 

OF

 

THE

 D

UCTWORK

 

•  Keep it simple. Plan for a minimum of bends and joints.

 

•  Keep the length of insulated ducts to a minimum.

 

•  Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would cause 

clogging of the filters and recovery module.

 

•  If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.

3.5 C

ALCULATING

 D

UCT

 

SIZE

Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values. 
Avoid installing ducts that will have to carry air flows near the maximum values and never install a duct if its air flow exceeds 
the maximum value.

D

UCT

 D

IAMETER

R

ECOMMENDED

 A

IR

 F

LOW

M

AXIMUM

 A

IR

 F

LOW

4” Ø (102 

MM

)

40 

CFM

 (19 

L

/

S

 

OR

 68 

M

³/

H

)

60 

CFM

 (28 

L

/

S

 

OR

 102 

M

³/

H

)

5” Ø (127 

MM

)

75 

CFM

 (35 

L

/

S

 

OR

 127 

M

³/

H

)

110 

CFM

 (52 

L

/

S

 

OR

 187 

M

³/

H

)

6” Ø (152 

MM

)

120 

CFM

 (57 

L

/

S

 

OR

 204 

M

³/

H

)

180 

CFM

 (85 

L

/

S

 

OR

 306 

M

³/

H

)

NOTE:  Examples 3.5.1 and 3.5.2 use imperial units. The same calculation applies to metric units.

 3.5.1 

E

XAMPLE

 

OF

 

CALCULATION

 Problem:

 My installation requires two exhaust registers (one for the kitchen, and the other for 

the bathroom). I will connect these registers to a main duct which will connect to the unit (high 
speed performance value of 140 cfm). What size of duct should I use for the main exhaust duct 
and for both end branches leading to the registers? (See illustration at right.)

 Solution:

 Simplified method. (For a more detailed method of calculating duct size, refer to the 

ASHRAE or HRAI HANDBOOK.)

 

Main duct: Table indicates for a 6” Ø duct: recommended air flow: 120 cfm, maximum air flow: 
180 cfm. The 140 cfm high speed air flow is close enough to the recommended value (120) 
and far away enough from the maximum value (180). Therefore, a 6” Ø duct or larger is an 
appropriate choice for the main exhaust duct.

 

End branches: Each end branch will have to transport a 70 cfm air flow (140 divided by 2). Table 
indicates for a 5” Ø duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The high 
speed air flow of 70 cfm is close enough to the recommended value (75) and far away enough 
from the maximum value (110). Therefore, a 5” Ø duct or larger is an appropriate choice for both 
end branches.

 

NOTE:  A 4” Ø duct would have been too small because the maximum acceptable value for a 4” Ø duct is 60 cfm.

 

3.5.2  Example of a design for a fully ducted system with a unit having a high speed performance of 160 cfm.

VI0016

E

ND

 

BRANCHES

M

AIN

 

BRANCH

6" Ø, 140 

CFM

5" Ø, 

70 

CFM

VI0017

4" Ø, 47 

CFM

5" Ø, 93 

CFM

5" Ø, 67 

CFM

4"

4"

4"

4"

4"

4"

4"

5"

5"

5"

5"

6"

6"

6" Ø, 160 

CFM

6" Ø, 160 

CFM

5" Ø, 86 

CFM

5" Ø, 62 

CFM

4" Ø, 24 

CFM

4" Ø, 

37 

CFM

4" Ø, 

46 

CFM

5" Ø, 

74 

CFM

Summary of Contents for 60H-V+

Page 1: ...V These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Canada 21781...

Page 2: ...prong Do not use an extension cord 8 Do not install in a cooking area or connect directly to any appliances 9 Do not use to exhaust hazardous or explosive materials and vapors 10 When performing inst...

Page 3: ...IT 10 3 8 INSTALLING TWO EXTERIOR HOODS 11 3 9 CONNECTING THE DRAIN 11 4 CONTROLS 12 15 4 1 UNITS BOOTING SEQUENCE 12 4 2 INTEGRATED CONTROL 12 4 3 SPEED AND DEFROST SETTINGS FOR AVS E15 ECM ERV AVS E...

Page 4: ...MIN NORMAL DEFROST CYCLE MIN EXTENDED DEFROST CYCLE MIN C F DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OP...

Page 5: ...one level require at least one exhaust register at the highest level See figure at right 2 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM Stale air coming from the registers located at the hig...

Page 6: ...H V ECM HRV units have one front door and one back door while the AVS E15 HRV AVS E10 HRV 90H V and the 60H V units only have one door For these last models the unit door can be relocated on the back...

Page 7: ...onnect these registers to a main duct which will connect to the unit high speed performance value of 140 cfm What size of duct should I use for the main exhaust duct and for both end branches leading...

Page 8: ...gas furnace a gas water heater or a fireplace 3 6 2 CENTRAL DRAW POINT SYSTEM AS ILLUSTRATED IN SECTION 2 2 Stale air exhaust ductwork Same as for Fully Ducted System described on point 3 6 1 Fresh ai...

Page 9: ...on the furnace blower must be in operation when the unit is in operation VJ0063 A B METAL DUCT A B NOT LESS THAN 10 3 1 M MINIMUM 18 0 5 M B A VJ0064 MINIMUM 3 0 9 M A B NOT LESS THAN 10 3 1 M Stale a...

Page 10: ...the insulation over the joint and tuck in between the inner and outer rings of the double collar 4 Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it comple...

Page 11: ...r it is recommended for climates where the outdoor temperature typically remains below 25 C 13 F over a 24 hour period for several days in a row combined with an indoor humidity of 40 or higher VO0258...

Page 12: ...uence the integrated control LED will light GREEN unit set in normal defrost or amber unit set in extended defrost for 3 seconds and then will shut off for 2 seconds After that the LED will light RED...

Page 13: ...tegrated control is in CFM setup mode HIGH speed Every 3 seconds the LED will blink RED the number of times corresponding to the chosen speed range See table below NOTE Anytime in setting process if t...

Page 14: ...tribution panel Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls Check if all wires are correctly inserted in their...

Page 15: ...the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower control For a furnace connected to a cooling system On some older thermostats ene...

Page 16: ...L listed CSA Certified line fuse 3A 3AG Type 2 If any of the original wire as supplied must be replaced use the same equivalent wire 3 Field wiring must comply with applicable codes ordinances and reg...

Page 17: ...ptional see notes 3 4 VE0086A Critical characteristic JU1 1 2 3 MED HI 3 2 1 HI MED JU1 FAN MOTORS SPEED SELECTION NOTES 1 Use specified UL listed CSA Certified line fuse 3A 3AG Type 2 If any of the o...

Page 18: ...otor J5 1 J5 3 J7 2 J7 1 J4 1 J4 3 J6 2 J6 1 K1 K3 K2 J9 1 J9 2 J9 3 J4 2 J9 4 Exhaust fan motor capacitor Supply fan motor capacitor J8 1 J8 2 J8 4 J8 5 K4 J12 2 J12 1 A1 Damper motor J3 2 J3 1 J2 2...

Page 19: ...ation at right Be sure to connect the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections 4 Note the CFM value from balancing chart on unit 5 Repe...

Page 20: ...207 18207 18207 18207 18207 18207 18207 3 EXHAUST DAMPER SPRING 1 18221 18221 18221 18221 18221 18221 18221 18221 4 MOTOR ASSEMBLY 2 18198 18198 18197 18197 18198 18198 18197 18197 5 BALANCING TOOL 2...

Page 21: ...he wires are correctly connected Inspect every wire and replace any damaged ones If wires are hidden into walls test the control using a shorter wire 2 There is no outside temperature displayed on Alt...

Page 22: ...ED LED At power up LED lights up in RED and there is a clicking sound coming from electrical compartment but damper does not move Ice or other things hindering the damper movement J12 unconnected or b...

Page 23: ...otor capacitor may be defective Tranformer wire s bad connection The transformer or the PCB may be defective Plug exhaust motor to J4 connector and supply motor to J5 connector If supply motor works b...

Page 24: ...g the button and LED flashes RED after 20 seconds The J4 connector may be misconnected or there may be a bad contact The JU1 jumper may be mispositioned The PCB may be defective The motor may be defec...

Reviews: