background image

6

2.  TYPICAL INSTALLATIONS (

CONT

D

)

2.4 A

TTIC

 I

NSTALLATION

 

FOR

 AVS E15 ECM ERV O

NLY

All three types of installation can be used in the attic (Fully ducted, Central Draw Point or Simplified). The example shown below is a 
Simplified Installation (connection to a forced air system).

NOTE:  To get the most of your ERV unit, the ambient temperature around the unit should be conditioned. If the unit has to be installed 

in a unconditioned space, the heat gains or losses from the unit and the ducts could increase the operation costs of the unit.

CAUTION

•  Due to the potential temperature difference between the attic and the rest of the house, all unit ducts must be insulated.
•  The attic temperature must always be above 10°C (50°F) and under 50°C (122°F).

Stale air is exhausted to the outdoors. Fresh air from outdoors is filtered and supplied 
to the return (plenum) of the forced air unit. See figure at right.
To avoid cross-contamination and achieve the highest efficiencies, the forced air 
system blower must always be ON.

NOTE:  Home with multiple forced air systems should have one unit on each system.

VH0076

3. INSTALLATION

3.1 I

NSPECT

 

THE

 C

ONTENT

 

OF

 

THE

 B

OX

Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, ports, power cord, etc.

3.2 U

NIT

 D

OOR

(

S

)

The AVS E15 ECM ERV, AVS E15 ECM HRV, 90H-V ECM ERV and the 
90H-V ECM HRV units have one front door and one back door while the 
AVS E15 HRV, AVS E10 HRV, 90H-V+ and the 60H-V+ units only have one 
door. For these last models, the unit door can be relocated on the back of the 
unit. This can be helpful to optimize duct configuration while keeping access 
for unit maintenance. To change door location, follow these steps:

 

A.

  Remove both door lower mechanical screws no. 8-32 x 1” (

1

) and set 

aside.

 

B.

 Open 

(

2

) and lift out the door (

3

).

To remove unit back panel, repeat steps 

A

 and 

B

, but instead of removing 

2 mechanical screws, there are 4 mechanical screws to be removed. Hang 
the door to the back of the unit and secure it by tightening its both lower 
mechanical screws. Hang back panel to the front of the unit and secure it by 
tightening its four metal screws.

VO0149

A

B

3

2

1

3.3 L

OCATING

 

THE

 U

NIT

Choose an appropriate location for the unit.

 

•  Within an area of the house 

where the ambient temperature is kept 

between 10°C (50°F) and 40°C (104°F)

.

 

•  Away from living areas (dining room, living room, bedroom), if possible.

 

•  So as to provide easy access to the interior of the unit, for quarterly and 

annual maintenance.

 

•  Close to an exterior wall, so as to limit the length of the insulated flexible 

duct to and from the unit.

 

•  Away from hot chimneys and other fire hazards.

 

•  Allow for a power source (standard 3-prong grounding outlet).

 

•  Close to a drain. If no drain is close by, use a pail to collect run-off.

Hang the unit with the four chains and springs provided.
See illustration at right.

VD0205

CAUTION

Make sure the unit is level.

Summary of Contents for 60H-V+

Page 1: ...V These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Canada 21781...

Page 2: ...prong Do not use an extension cord 8 Do not install in a cooking area or connect directly to any appliances 9 Do not use to exhaust hazardous or explosive materials and vapors 10 When performing inst...

Page 3: ...IT 10 3 8 INSTALLING TWO EXTERIOR HOODS 11 3 9 CONNECTING THE DRAIN 11 4 CONTROLS 12 15 4 1 UNITS BOOTING SEQUENCE 12 4 2 INTEGRATED CONTROL 12 4 3 SPEED AND DEFROST SETTINGS FOR AVS E15 ECM ERV AVS E...

Page 4: ...MIN NORMAL DEFROST CYCLE MIN EXTENDED DEFROST CYCLE MIN C F DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OP...

Page 5: ...one level require at least one exhaust register at the highest level See figure at right 2 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM Stale air coming from the registers located at the hig...

Page 6: ...H V ECM HRV units have one front door and one back door while the AVS E15 HRV AVS E10 HRV 90H V and the 60H V units only have one door For these last models the unit door can be relocated on the back...

Page 7: ...onnect these registers to a main duct which will connect to the unit high speed performance value of 140 cfm What size of duct should I use for the main exhaust duct and for both end branches leading...

Page 8: ...gas furnace a gas water heater or a fireplace 3 6 2 CENTRAL DRAW POINT SYSTEM AS ILLUSTRATED IN SECTION 2 2 Stale air exhaust ductwork Same as for Fully Ducted System described on point 3 6 1 Fresh ai...

Page 9: ...on the furnace blower must be in operation when the unit is in operation VJ0063 A B METAL DUCT A B NOT LESS THAN 10 3 1 M MINIMUM 18 0 5 M B A VJ0064 MINIMUM 3 0 9 M A B NOT LESS THAN 10 3 1 M Stale a...

Page 10: ...the insulation over the joint and tuck in between the inner and outer rings of the double collar 4 Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it comple...

Page 11: ...r it is recommended for climates where the outdoor temperature typically remains below 25 C 13 F over a 24 hour period for several days in a row combined with an indoor humidity of 40 or higher VO0258...

Page 12: ...uence the integrated control LED will light GREEN unit set in normal defrost or amber unit set in extended defrost for 3 seconds and then will shut off for 2 seconds After that the LED will light RED...

Page 13: ...tegrated control is in CFM setup mode HIGH speed Every 3 seconds the LED will blink RED the number of times corresponding to the chosen speed range See table below NOTE Anytime in setting process if t...

Page 14: ...tribution panel Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls Check if all wires are correctly inserted in their...

Page 15: ...the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower control For a furnace connected to a cooling system On some older thermostats ene...

Page 16: ...L listed CSA Certified line fuse 3A 3AG Type 2 If any of the original wire as supplied must be replaced use the same equivalent wire 3 Field wiring must comply with applicable codes ordinances and reg...

Page 17: ...ptional see notes 3 4 VE0086A Critical characteristic JU1 1 2 3 MED HI 3 2 1 HI MED JU1 FAN MOTORS SPEED SELECTION NOTES 1 Use specified UL listed CSA Certified line fuse 3A 3AG Type 2 If any of the o...

Page 18: ...otor J5 1 J5 3 J7 2 J7 1 J4 1 J4 3 J6 2 J6 1 K1 K3 K2 J9 1 J9 2 J9 3 J4 2 J9 4 Exhaust fan motor capacitor Supply fan motor capacitor J8 1 J8 2 J8 4 J8 5 K4 J12 2 J12 1 A1 Damper motor J3 2 J3 1 J2 2...

Page 19: ...ation at right Be sure to connect the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections 4 Note the CFM value from balancing chart on unit 5 Repe...

Page 20: ...207 18207 18207 18207 18207 18207 18207 3 EXHAUST DAMPER SPRING 1 18221 18221 18221 18221 18221 18221 18221 18221 4 MOTOR ASSEMBLY 2 18198 18198 18197 18197 18198 18198 18197 18197 5 BALANCING TOOL 2...

Page 21: ...he wires are correctly connected Inspect every wire and replace any damaged ones If wires are hidden into walls test the control using a shorter wire 2 There is no outside temperature displayed on Alt...

Page 22: ...ED LED At power up LED lights up in RED and there is a clicking sound coming from electrical compartment but damper does not move Ice or other things hindering the damper movement J12 unconnected or b...

Page 23: ...otor capacitor may be defective Tranformer wire s bad connection The transformer or the PCB may be defective Plug exhaust motor to J4 connector and supply motor to J5 connector If supply motor works b...

Page 24: ...g the button and LED flashes RED after 20 seconds The J4 connector may be misconnected or there may be a bad contact The JU1 jumper may be mispositioned The PCB may be defective The motor may be defec...

Reviews: