SETTING
Chart 5: ALARM SYSTEM ON/OFF NOTICE, TERMINAL no. 5
DIP 3
NOTICE (sound)
OFF (default setting)
STI is open = alarm system is disarmed (OFF), STI 12V = alarm system is armed (ON).
Flashes as per PONT 1
ON
STI is open = alarm system is disarmed (OFF), STI 0V = alarm system is armed (ON). Flashes as per PONT 1
Chart 2: ALARM TIMING
DIP 1
Alarm timing
OFF (default setting)
3 minutes
ON
8 minutes
Chart 4: ALARM INPUT POLARITY OF SOUNDER COMMAND, TERMINAL no. 3
DIP 2
Terminal 3
OFF (default setting)
Positive-missing (alarm if disconnected or 0V)
ON
Negative-missing (alarm if disconnected or +12V)
Chart 6: TONE SELECTION
DIP 4
TONE
FREQUENCY LIMITS (Hz)
OFF (default setting)
CERTIFIED
Increasing-Continuous-Decreasing-
Continuous
1.400 ÷ 1.800
ON
Increasing-Decreasing (NFC 48-265)
1.400 ÷ 1.600
SOUND IS ACTIVATED ON STI TERMINAL (3 BEEPs while arming and a long BEEP while disarming)
Chart 9: DAILY ALARMS COUNTING
PONT 3 (R85)
ALARMS NUMBER DURING THE 24 HOURS AFTER THE FIRST ALARM
CONNECTED (default setting)
Infinite alarms
CUT
MAX 4 DAILY ALARMS (each alarm is counted only if it lasts at least 30 seconds)
IN CASE MORE THAN 4 DAILY ALARMS OCCUR, THE SOUNDER FLASHES WITH NO SOUND
(STI resets alarm counting)
Terminal 5
Anomaly output.
Open-collector at 0V = no anomaly