SETTING 

        

 

 

 
 
 

 
 

 
 
 
 
 
 

 

Chart 5: ALARM SYSTEM ON/OFF NOTICE, TERMINAL no. 5 

DIP 3 

NOTICE (sound) 

OFF (default setting) 

STI is open = alarm system is disarmed (OFF), STI 12V = alarm system is armed (ON).  
Flashes as per PONT 1 

ON 

STI is open = alarm system is disarmed (OFF), STI 0V = alarm system is armed (ON). Flashes as per PONT 1 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chart 2: ALARM TIMING 

DIP 1 

Alarm timing 

OFF (default setting) 

3 minutes 

ON 

8 minutes 

Chart 4: ALARM INPUT POLARITY OF SOUNDER COMMAND, TERMINAL no. 3 

DIP 2 

Terminal 3 

OFF (default setting) 

Positive-missing (alarm if disconnected or 0V) 

ON 

Negative-missing (alarm if disconnected or +12V) 

Chart 6: TONE SELECTION 

DIP 4 

TONE 

FREQUENCY LIMITS (Hz) 

OFF (default setting) 
CERTIFIED 

Increasing-Continuous-Decreasing-
Continuous 

1.400 ÷ 1.800 

ON 

Increasing-Decreasing (NFC 48-265) 

1.400 ÷ 1.600 

 

SOUND IS ACTIVATED ON STI TERMINAL (3 BEEPs while arming and a long BEEP while disarming) 

Chart 9: DAILY ALARMS COUNTING 

PONT 3 (R85) 

ALARMS NUMBER DURING THE 24 HOURS AFTER THE FIRST ALARM  

CONNECTED (default setting) 

Infinite alarms 

CUT 

MAX 4 DAILY ALARMS (each alarm is counted only if it lasts at least 30 seconds) 
IN CASE MORE THAN 4 DAILY ALARMS OCCUR, THE SOUNDER FLASHES WITH NO SOUND 
(STI resets alarm counting) 

Terminal 5 

Anomaly output. 
Open-collector at 0V = no anomaly 

Summary of Contents for RIALTO L

Page 1: ...timings alarm counting optical and acoustic signaling of System ON OFF arming disarming electronic circuit protected against polarity inversion and tropicalized by resin immersion microprocessor self...

Page 2: ...TERMINAL NEGATIVE INPUT FOR SOUND BLOCK It activates the sound interruption trigger by taking a negative 0V to terminal no 4 D STI TERMINAL SYSTEM STATUS NOTICE PERMANENT MOMENTARY ALARM SYSTEM ON OFF...

Page 3: ...5 STI to 12V for 10 seconds then take away the voltage from the terminal These steps launch the test which will last 60 seconds During the test the sounder verifies its own functioning and notifies an...

Page 4: ...ive missing alarm if disconnected or 0V ON Negative missing alarm if disconnected or 12V Chart 6 TONE SELECTION DIP 4 TONE FREQUENCY LIMITS Hz OFF default setting CERTIFIED Increasing Continuous Decre...

Page 5: ...nd the power supply to the control panel 5 Close both internal and external covers using the screws provided 6 Battery must have UL94 HB flammability rate 7 Power supply must be of SELV type Attention...

Page 6: ...5 mA Vc 12V 0 3 mA Vc 0V Open collector 10mA max LED flashing unit life 1 000 000 flashes Timing 3 minutes settable at 8 minutes Battery capacity 12V 2 0 Ah Switch tamper range N C 0 2 A max Fundament...

Page 7: ...MA SE RTL0 03 01 Manuale Rialto Triade Lido Eng rev1 Page 7 of 8 NOTE...

Page 8: ...MA SE RTL0 03 01 Manuale Rialto Triade Lido Eng rev1 Page 8 of 8 Via del Lavoro 10 30030 Salzano VE Tel 39 041 5740374 Fax 39 041 5740388 Web site www venitem com E mail info venitem com...

Reviews: