MA-SE-RTL0-03-01 Manuale Rialto Triade Lido Eng rev1 

 

    Page 3 of 8 

DIP 3 in ON position 

 

Giving a negative (0V) to terminal no. 5, all LEDs of the flashing unit flash 3 times (ON). Anomalies are reset to zero. 

 

Taking away the negative, all LEDs stay lighted up steady for 5 seconds (OFF) and the complete sounder test is launched. 
In case of anomalies, they are duly notified. 
 

Activated sounds: To activate sounds (three BEEPs while arming and a long BEEP while disarming) set DIP 4 in ON position. 

 
E) RES TERMINAL, NEGATIVE INPUT OF FLASHING UNIT RESET 
    When set (through PONT no. 2), it stops the flashing activity of the flashing unit by taking terminal no. 6 to 0V for one second. 
 
F) OUT ANM TERMINAL AND ANOMALY LED 

The sounder is managed by a microcontroller able to check if the battery recharging process is going on properly, if the battery 
status  is  good,  if  the  speaker  is  good  or  faulty  and  if  the  power  amps  are  in  good  condition.  In  case  of  anomaly,  the  open-
collector  terminal  OUT  ANM  opens  and  LD1 LED on the sounder board shows the fault  type by making a  certain number of 
flashes followed by a short pause. 
The microprocessor automatically performs the battery current test every 4 hours. Moreover, it continuously performs other 
tests. If the sounder is correctly supplied, the anomaly output (terminal no. 7) usually stays at 0V (max consumption 50mA). If 
any of the tests performed fails, the anomaly output disconnects from ground and becomes free
When  the  sounder  receives  power  supply  for  the  first  time  (13V  or  battery),  to  make  installation  easier,  anomalies  are 
automatically  reset  to  zero  when  their  cause  disappears.  After  the  first  alarm  trigger,  anomalies  are  reset  to  zero  only 
tC, RES or a command to STI. 
To launch the remote test, take terminal no. 5 (STI) to 12V for 10 seconds, then take away the voltage from the terminal. 
These steps launch the test which will last 60 seconds. During the test, the sounder verifies its own functioning and notifies 
any anomalies both through the anomaly output (OUT ANM) and the anomaly LED, as indicated in the chart below. To reset 
the  anomaly  to  zero,  remove  its  cause  first,  then  wait  10  seconds  and  take  terminal  no.  5  (STI)  to  12V  for  at  least  10 
seconds. When the command is taken away from teC for a very short time lapse, all anomalies are reset to zero 
with the exception of those concerning the battery. After 4 hours from battery restore, the sounder performs the tests 
once again and updates the anomaly notices, including battery anomaly.  
In case any anomaly appears, the flashing unit LEDs flash faster and the acoustic notice at arming becomes a single BEEP.  
    

ANOMALY NOTICE CHART 

 

ANOMALY red LED 

ANOMALY OUTPUT (OUT NO. 7) 

SPEAKER INTERRUPTION (test performed every 10 s) 

1 FLASH 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

NO RECHARGE CURRENT (recharge current is lower than 11.5V) 
(test performed every 10 s) 

2 FLASHES 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

BATTERY IS DISCONNECTED, IS LOWER THAN 2.5 V 
(test performed every 4 hours) 

3 FLASHES 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

BATTERY IS INSUFFICIENT, IS LOWER THAN 10 V 
(test performed every 4 hours) 

4 FLASHES 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

INTERNAL BATTERY RESISTOR > 3.5 OHM 
(test performed every 4 hours) 

5 FLASHES 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

SPEAKER POWER AMPs ARE INTERRUPTED 
(test performed every 10 seconds) 

6 FLASHES 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

SOUNDER IS NOT POWERED OR SOUNDER MICROPROCESSOR IS 
FAULTY  

OFF 

OUTPUT OPEN (OPEN COLLECTOR OFF) 

NO ANOMALIES 

 

OFF 

OUTPUT TO GROUND, 0V  
(OPEN COLLECTOR IS ACTIVE) 

 
 
 
G) ANTI-OPENING AND ANTI-REMOVAL TAMPER 

CONNECTION 

Connect TAMPER terminals no. 8 and no. 9 to the 
tamper line coming from the control panel. 

 
H) BATTERY CONNECTION 

Connect  the  12V  battery  to  the  corresponding 
connector faston. 
 

    

 

 

Summary of Contents for RIALTO L

Page 1: ...timings alarm counting optical and acoustic signaling of System ON OFF arming disarming electronic circuit protected against polarity inversion and tropicalized by resin immersion microprocessor self...

Page 2: ...TERMINAL NEGATIVE INPUT FOR SOUND BLOCK It activates the sound interruption trigger by taking a negative 0V to terminal no 4 D STI TERMINAL SYSTEM STATUS NOTICE PERMANENT MOMENTARY ALARM SYSTEM ON OFF...

Page 3: ...5 STI to 12V for 10 seconds then take away the voltage from the terminal These steps launch the test which will last 60 seconds During the test the sounder verifies its own functioning and notifies an...

Page 4: ...ive missing alarm if disconnected or 0V ON Negative missing alarm if disconnected or 12V Chart 6 TONE SELECTION DIP 4 TONE FREQUENCY LIMITS Hz OFF default setting CERTIFIED Increasing Continuous Decre...

Page 5: ...nd the power supply to the control panel 5 Close both internal and external covers using the screws provided 6 Battery must have UL94 HB flammability rate 7 Power supply must be of SELV type Attention...

Page 6: ...5 mA Vc 12V 0 3 mA Vc 0V Open collector 10mA max LED flashing unit life 1 000 000 flashes Timing 3 minutes settable at 8 minutes Battery capacity 12V 2 0 Ah Switch tamper range N C 0 2 A max Fundament...

Page 7: ...MA SE RTL0 03 01 Manuale Rialto Triade Lido Eng rev1 Page 7 of 8 NOTE...

Page 8: ...MA SE RTL0 03 01 Manuale Rialto Triade Lido Eng rev1 Page 8 of 8 Via del Lavoro 10 30030 Salzano VE Tel 39 041 5740374 Fax 39 041 5740388 Web site www venitem com E mail info venitem com...

Reviews: