12
106309-03 - 4/19
III. Pre-Installation and Boiler Mounting
G. General (continued)
WARNING
Asphyxiation Hazard. Adequate combustion and
ventilation air must be provided to assure proper
combustion. Install combustion air intake per
Section IV “Venting”.
F. The boiler should be located
so as to minimize
the length of the vent system. Locate combustion air
pipe termination away from areas that may contaminate
combustion air, (see Table 4). In particular, avoid
areas near chemical products containing chlorines,
chlorofluorocarbons, paint removers, cleaning solvents
and detergents. Avoid areas containing saw dust, loose
insulation fibers, dry wall dust etc.
NOTICE
Avoid operating this boiler in an environment
where sawdust, loose insulation fibers, dry wall
dust, etc. are present. If boiler is operated under
these conditions, the burner interior and ports
must be cleaned and inspected daily to insure
proper operation.
G. General.
1. Phantom X boilers are intended for installations in
an area with a floor drain, or in a suitable drain pan
to prevent any leaks or safety relief valve discharge
resulting in property damage.
2. Phantom X boilers are not intended to support
external piping and venting. All external piping and
venting must be supported independently of the
boiler.
3. Phantom X boilers must be installed level to prevent
condensate from backing up inside the boiler.
4. Boiler Installation:
a. For basement installation provide a solid level
base such as concrete where floor is not level or
where water may be encountered on the floor
around boiler. Floor must be able to support
Table 5: Vent Pipe Clearances to Combustible Material
Boiler Clearances to Combustible (and Non-
Combustible) Material:
Models PHNTM399C and PHNTM500C:
These boilers are listed for closet installation with the
following minimum clearances – Top = 1 in. (25 mm),
Front = 1 in. (25 mm), Left Side = 10 in. (250 mm),
Right Side = 2 in. (50 mm), Rear = *6 in. (150 mm)
Models PHNTM600C, PHNTM700C and
PHNTM800C:
These boilers are listed for alcove installation with the
following minimum clearances – Top = 1 in. (25 mm),
Front = Open, Left Side = 10 in. (250 mm), Right Side
= 2 in. (50 mm), Rear = *6 in. (150 mm)
* Note:
When boiler is vented vertically, the minimum
clearance from the rear of the jacket is increased to
18 in. (460 mm) with a short radius 90° elbow
provided in order to provide adequate space at boiler
rear for installation of vent and air intake piping and
service access.
Boiler Service Clearances – Applicable to all Boiler
Models:
Top = 24 in. (610 mm), Front = 24 in. (610 mm), Left
Side = 24 in. (610 mm), Right Side = 24 in. (610 mm),
Rear = 24 in. (610 mm)
The above clearances are recommended for service
access but may be reduced to the Combustible Material
Clearances provided:
1. The boiler front is accessible through a door.
2. Access is provided to the condensate trap located on
the left side of boiler.
3. Access is provided to thermal link located at the
boiler rear.
Listed Direct
Vent System
Vent Pipe Material
Vent Pipe
Direction
Enclosure
Vent Pipe
Nominal Diameter
Minimum
Clearance to
Combustible
Material
Standard
Two-Pipe CPVC/PVC Vent and PVC Combustion Air Intake
CPVC/PVC
Vertical or
Horizontal
Unenclosed
at all Sides
3 in. (80 mm),
4 in. (100 mm or 110 mm)
6 in. (150 mm or 160 mm)
1 in. (25 mm)
Optional
Two-Pipe Rigid Polypropylene Vent (or, Flexible Polypropylene
Liner for Vertical Venting only) and Rigid Polypropylene or PVC
Combustion Air Intake
Rigid Polypropylene (or,
Flexible Polypropylene
Liner for Vertical Venting
only)
3 in. (80 mm),
4 in. (100 mm or 110 mm)
6 in. (150 mm or 160 mm)
1 in. (25 mm)
Optional
Two-Pipe Stainless Steel Vent and Galvanized Steel or PVC
Combustion Air Intake
Stainless Steel
3 in. (80 mm),
4 in. (100 mm or 110 mm)
6 in. (150 mm or 160 mm)
1 in. (25 mm)
weight of boiler, water and all additional system
components.
b. Boiler must be level to prevent condensate from
backing up inside the boiler.
c. Provide adequate space for condensate piping or
a condensate pump if required.
Summary of Contents for Phantom-X Series
Page 49: ...49 106309 03 4 19 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 63: ...63 106309 03 4 19 VIII Electrical continued Figure 40 Ladder Diagram...
Page 64: ...64 106309 03 4 19 VIII Electrical continued Figure 41 Wiring Connections Diagram 2...
Page 73: ...73 106309 03 4 19 IX System Start up continued Figure 47 Operating Instructions...
Page 124: ...124 106309 03 4 19 XIII Service Parts continued...
Page 130: ...130 106309 03 4 19 XIII Service Parts continued...
Page 133: ...133 106309 03 4 19 XIII Service Parts continued 10A 10B 10C 10D 10G...
Page 139: ...139 106309 03 4 19...