Solar Pump Controller Manual
29
F-31
Output terminal
Y1
4:Frequency level signal detection
5: In operating
6:Reversal operation
7:Solar pump control under voltage
8:Overload pre-alarm
9:Output frequency reach upper
frequency limit
10:Output frequency reach lower
frequency limit
11:Exterior fault close-down
12:Timer times up
13:Counter reach maximum value
14:Counter reach setting value
15:PID feedback quantity upper limit
alarm
16:PID feedback quantity lower limit
alarm
17:Sensor disconnect
18:Program operation cycle period
accomplish
19:Program operation step
accomplish
3
●
21FH
F-32
Output terminal
Y2
7
●
220H
F-33
Frequency range
can be detected
0.00
~
50.00Hz
1.00
●
221H
F-34
Output frequency
detection range
0.00
~
400.0Hz
30.00
●
222H
F-35
Output frequency
detection delay
time
0.0
~
20.0 second
0.0
●
223H
F-36
Overload pre-alarm
range
50
~
200%
150
●
224H
F-37
Overload pre-alarm
delay time
0.0
~
20.0 second
1.0
●
225H
F-38
Timer setting
values
1
~
65000 second
1
●
226H
F-39
Counter maximum
Value
1
~
65000
1000
●
227H
F-40
Counter setting
Value
1
~
Counter maximum value
100
●
228H
F-41
VS1 terminal input
Voltage lower limit
0.00V
~
[F-42]
0.00
●
229H