Solar Pump Controller Manual
24
E-38
DC break time
while start
0.0
~
10.0s
0.0
●
126H
E-39
Jump frequency
1
0.00
~
400.0Hz(Fmax)
0.00
●
127H
E-40 Jump frequency
2
0.00
~
400.0Hz(Fmax)
0.00
●
128H
E-41
Jump frequency
3
0.00
~
400.0Hz(Fmax)
0.00
●
129H
E-42
Jump frequency
range
0.00
~
5.00Hz
0.00
●
12AH
E-43
Fault reset
times
0:Off
1
~
3: On
0
●
12BH
E-44
Fault reset wait
time
0.1
~
20.0 s
1.0
●
12CH
E-45 Warm
time
0.0
~
6500s
0.0
●
12DH
E-46 Run
direction
0: Default
1:Opposite to default
2:Forbid REV
0
〇
12EH
E-47
RUN/REV dead
time
0.0
~
10.0s
0.0
●
12FH
E-48 Cool fan control
0:Fan run after electrify
1:Fan stop related to temperature,
work while running
2:Fan stop while machine stop,
run related to temperature
※
●
130H
E-49
Protection
function
selection
LED “0”digit: OV protection
selection
0:Invalid
1:Valid
LED“00”digit: Open phase at output
side
0:Invalid
1:Valid
LED“000”digit:input phase lack
0:Invalid
1:Valid
LED “0000” digit: inverter OL/ OT
protection mode
0:Free stop
1:Limit current and run
0
※
11
●
131H
E-50
Electric
thermistor
coefficient
30%
~
120%(invalid if under 30%)
0
●
132H
E-51 Current limit for
stall protection
100%
~
250%
160 G
120 P
●
133H
E-52 Bus voltage for
stall protection
110
~
150%
128%
●
134H