Summary of Contents for SI10

Page 1: ...Version V1 4 in Year 2015...

Page 2: ...ure to carefully read the manual about safety installation operation and maintenance The safe operation depends on the proper processes of choosing models carrying installation operation and maintenan...

Page 3: ...thout anti static measure otherwise it will cause the malfunction of frequency inverter 4 Please don t connect phase shifter capacitance or LC RC noise filter to the output circuit of frequency invert...

Page 4: ...heck and confirm the application range of the machine and equipments once more Otherwise it will cause accidents 2 Please don t touch the cooling fan and braking resistance to check the temperature Ot...

Page 5: ...ce of the load equipment To avoid it you can set up jumping frequency 5 As output voltage of the inverter is pulse wave type if there is capacity which can improve power factor or pressure sensitive r...

Page 6: ...0 480 560 25 0 60 15 15 380 19 5 780 480 560 32 0 60 18 5 18 5 380 23 4 780 480 560 38 0 60 22 22 380 28 6 780 480 560 45 0 60 30 30 380 39 780 480 560 60 0 60 37 37 380 48 1 780 480 560 75 0 60 45 45...

Page 7: ...l hood upwardly inclines around 15 degrees and inserts the top fixed flat into the fixed hole in the front cover Then slightly press the tail hood downward While your hear Ka it means that the tail ho...

Page 8: ...40G 122 112 182 171 154 5 145 5 SI10 S2 R75G SI10 S2 1R5G SI10 T3 R75G SI100 T3 1R5G SI10 T3 2R2G SI10 D3 2R2G 159 147 2 246 236 157 5 148 5 5 SI10 D3 3R7G SI10 D5 3R7G SI10 D5 5R5G SI10 D5 7R5G 195 1...

Page 9: ...verter W H D H2 W1 H1 Installation aperture SI10 D5 015G 235 345 200 311 160 331 5 7 SI10 D5 018G SI10 D5 022G 255 410 225 370 180 395 7 SI10 D5 030G SI10 D5 037G 305 570 260 522 180 550 9 SI10 D5 045...

Page 10: ...al 9 H1 H H2 D W1 W Frequency inverter W H D H2 W1 H1 Installation aperture SI10 D5 132G 500 780 340 708 350 755 11 SI10 D5 160G 650 1060 400 950 400 1023 16 SI10 D5 185G SI10 D5 200G SI10 D5 220G 750...

Page 11: ...ation RS485 A B COM Y2 Y1 COM Open set electrode output GND A02 F 62 Selection output Analog input signal 10V signal supply power 10V GND Pulse frequency PUL REV REV X5 Electrical machine M V W U Anal...

Page 12: ...Y2 X2 X1 X3 X4 X5 X6 COM PUL GND AO1 AO2 VS1 VS2 AS 10V 10V GND A B FWD 2 5 2 Control terminals menu Categ ory Terminal name Function Control signal COM Common terminal FWD Forward turn command Short...

Page 13: ...programmable setting motion targets Max output DC24V 50mA Y2 Output signal 3 Open collector output programmable setting motion targets Max output DC24V 50mA Analog output input signal GND Output commo...

Page 14: ...terface Modify given frequency or PID or given torque while at standby or monitoring state While given frequency or PID or given torque are set by keyboard Shift key Select digit of function no modifi...

Page 15: ...e V indicator light at the same time the 4 digit digital display value is the amount of PID feedback State indicators FWD On Frequency inverter turns forward FWD Flashing Frequency inverter reverses F...

Page 16: ...y light flashing off Display input voltage Display electrical machine rotational speed Display PID stting quantity Display PID feedback quantity SET key is used switch display items while inverter is...

Page 17: ...page Standby or running mode Query parameter number Enter function menu interface Function parameter number Select up down key to chang digit Select up down key to chang digit Enter parameter value mo...

Page 18: ...mit voltage according to certain ACC speed If output frequency is still lower than H 32 lowest run frequency while it is lower than upper limit voltage it accelerates by E 13 ACC time 4 Automatic dorm...

Page 19: ...with proper capacity o C 2 Dec over current 1 Deceleration time is too short 2 Potential load or inertia is too big 3 Frequency inverter capacity is too low 1 Lengthen deceleration time 2 Connect exte...

Page 20: ...e machine in running when momentary stop occurs 4 V F curve setup or torque boost is not suitable 1 Select frequency inverter with proper capacity 2 Lengthen acceleration time 3 Restart after the moto...

Page 21: ...hnical support 2 Ask for technical support Err4 Frequency inverter exterior fault Exterior exterminal action Check exterior device Err5 Swing frequency running parameters setting error User set the sw...

Page 22: ...1H E 02 Frequency reference main channel selection 0 Keyboard digital setting 1 Keyboard potentiometer 3 AS current signal 4 20mA 4 VS2 voltage signal 10V 10V 5 Terminal pulse signal 6 RS485 communica...

Page 23: ...REV JOG selections 0 REV 1 JOG 0 108H E 09 MAX frequency 0 50 400 0Hz 50 0 109H E 10 Upper limitation Lowest limitation MAX frequency 50 00 10AH E 11 Lowest limitation 0 00 upper limitation 0 00 10BH...

Page 24: ...8H E 25 JOG 0 00Hz upper limitation 5 00 119H E 26 JOG ACC time 0 1 6500 0s 2 0 11AH E 27 JOG DEC time 0 1 6500 0s 2 0 11BH E 28 Start frequency 0 00 60 00Hz 0 50 11CH E 29 Start frequency duration 0...

Page 25: ...RUN REV dead time 0 0 10 0s 0 0 12FH E 48 Cool fan control 0 Fan run after electrify 1 Fan stop related to temperature work while running 2 Fan stop while machine stop run related to temperature 130H...

Page 26: ...model 1 P model 0 13DH E 62 Stable time for speed track 0 20 10 00s 0 60 13EH E 63 Parameter change protection 0 Can change all parameter 1 Can only change parameter set by keyboard no 2 Can not chang...

Page 27: ...ault alarm 14 Acceleration and deceleration time selection terminal 1 15 Acceleration and deceleration time selection terminal 2 16 Frequency setting channel Selection terminal 1 17 Frequency setting...

Page 28: ...nly keyboard control effective 1 All control mode effective LED 1000 digit after fault reset terminal operation mode selection 0 Terminal control can restart directly 1 Terminal control first close do...

Page 29: ...dage factor 0 100 0 80 0 213H F 20 H 37 parameters pondage factor 0 100 0 90 0 214H F 21 H 38 parameters pondage factor 0 100 0 75 0 215H F 22 Dry run protection time 0 1 6000 0S 300 0 216H F 23 Dry r...

Page 30: ...it alarm 17 Sensor disconnect 18 Program operation cycle period accomplish 19 Program operation step accomplish 3 21FH F 32 Output terminal Y2 7 220H F 33 Frequency range can be detected 0 00 50 00Hz...

Page 31: ...lid 1 Both valid 2 Bipolar adjust valid but direction control invalid 0 230H F 49 VS2 terminal input bipolar control zero hysteresis band 0 00V 3 00V 0 20 231H F 50 AS terminal input current lower lim...

Page 32: ...Negative characteristic 0000 23AH F 59 Terminal analog input filter time constant 0 01 5 00 second 0 50 23BH F 60 Output terminal AO1 selection 0 Output signal close 1 Output frequency speed 2 Output...

Page 33: ...elonging Communication address H 01 Free setting voltage V1 0 0 H 03 3 0 301H H 02 Free setting frequency F1 0 0Hz H 04 1 00 302H H 03 Free setting voltage V2 H 01 H 05 28 0 303H H 04 Free setting fre...

Page 34: ...requency 15 00 30EH H 15 Start frequency duration 0 0 6500 0s 10 0 30FH H 16 PID keyboard number given 0 0 100 0 50 0 310H H 17 Feedback channel gain 0 01 5 00 1 00 311H H 18 Sensor maximum measuring...

Page 35: ...it time 0 1 6500 0s 30 0 322H H 35 Automatic dormancy voltage 0 1000V 323H H 36 Renew voltage in dormancy 0 1000V 324H H 37 Max MPPT voltage setting 0 1000V 325H H 38 Min MPPT voltage setting 0 1000V...

Page 36: ...53 Frequency 3 0 600 00HZ 40 00 330H H 54 Frequency step4 0 10 00HZ 0 10 331H H 55 Frequency 4 0 600 00HZ 45 00 332H H 56 Frequency step 5 0 10 00HZ 0 80 338H H 57 Frequency 5 0 600 00HZ 48 00 339H H...

Page 37: ...Communications timeout time 0 0 6500 0 second 10 0 347H H 72 RS485 Communication disconnection action mode 0 close down 1 Continued operation 0 348H H 73 Response delayed 0 001 1 000 second 0 005 349...

Page 38: ...1000V Factory setting H 36 Renew voltage in dormancy Range 0 1000V Factory setting H 37 Max MPPT voltage setting Range 0 1000V Factory setting H 38 Min MPPT voltage setting Range 0 1000V Factory setti...

Page 39: ...ge value Range 0 1000W Factory setting 10 MPPT search frequency step is opposite to H 45 and quadratic of output frequency It is proportional to H 46 Search frequency step according to different outpu...

Page 40: ...ange 0 10 00HZ Factory setting 0 15 H 53 Frequency 3 Range 0 600 00HZ Factory setting 40 00 H 54 Frequency step4 Range 0 10 00HZ Factory setting 0 10 H 55 Frequency 4 Range 0 600 00HZ Factory setting...

Page 41: ...t current 0 1A C03H C 4 Input power 0 1KW C04H C 5 DC Bus voltage V C05H C 6 Bus current 0 1A C06H C 7 PID give value or search frequency step while E 02 10 C07H C 8 PID feedback or CVT base voltage w...

Page 42: ...C1CH Input terminal connect disconnect state schematic diagram X5 terminal stage X6 terminal stage FWD terminal stage REV terminal stage X3 terminal stage X2 terminal stage X1 terminal stage X4 termin...