Chapter 3 Mechanical and Electrical Installation
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
36
2)
Matching the input voltage to the voltage requirements of the AC drive;
3)
The cable diameter and voltage resistance of the input and output shall meet the requirements;
4)
High voltage switches on the power supply side should have effective lightning protection
measures.
3.3.5 Wiring of the Control Circuit
The ACH200 series high voltage AC drive user I/O interface board provides 8 switch inputs,
8 switch outputs, 4 analogue inputs and 5 analogue outputs (switch and analogue can be extended
according to user requirements), while optional relay outputs are supported.
User IO terminal description:
Classifica
tion
Termi
nal
Functional description of the
terminal
Technical specification
Switching
Input
X1 Multi-function input option 1
1.
Optocoupler isolated input
with COM
2.
Input voltage must be 24 V
3.
Overhanging terminals
indicate disconnection
4.
Input impedance: 3.3K
5.
Where X8 can be used as a
high-speed pulse input
terminal
X2 Multi-function input option 2
X3 Multi-function input option 3
X4 Multi-function input option 4
X5 Multi-function input option 5
X6 Multi-function input option 6
X7 Multi-function input option 7
X8
Multi-function input option 8, for high
speed pulse output
Switching
Output
Y1 Multifunctional output option 1
1.
Optocoupler isolated input
with COM
2.
Where Y8 can be used as a
high-speed pulse output
terminal
3.
Default weak pull-up to 24V
4.
Weak pull-up impedance 12K
Y2 Multifunctional output option 2
Y3 Multifunctional output option 3
Y4 Multifunctional output option 4
Y5 Multifunctional output option 5
Y6 Multifunctional output option 6
Y7 Multifunctional output option 7
Y8
Multifunctional output option 8 for high
speed pulse output
Relays
Output
T01 Relay output terminal 1
Each relay has a normally
open/normally closed output and
the relays have a current carrying
capacity of 3A
T02 Relay output terminal 2
T03 Relay output terminal 3
T04 Relay output terminal 4
T05 Relay output terminal 5
T06 Relay output terminal 6
T07 Relay output terminal 7
T08 Relay output terminal 8
High
speed
pulse
Impulse
input
HDI
High-speed pulse input terminal
(common X8 terminal)
1.
Optocoupler isolated input
with COM
2.
Input voltage must be 24 V
3.
Overhanging terminals
indicate disconnection