Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
100
shifted two places to the
right & 0x3, selecting the
action when the busbar
detects a phase loss
1: Software input phase loss
warning
Other values: software input
phase failure
LED hundred digits: CPU
overload
0: off 1: on
LED thousand digits: grid
anomalies
0: off 1: on
FA.16
Motor overload
protection factor
0.0%~250.0%
100.0%
〇
△
0xA10
FA.17
Load
warning
checkout setting
LED one digit: checkout
selection (protection 1)
0: untested
1: Detecting excessive loads
2: Overload detection at
constant speed only
3: Detecting insufficient
load
4: Insufficient load detection
at constant speed only
LED ten digits: alarm
selection
0: Alarm, continue to run
1: Fail-safe operation and
free stop
LED
hundred
digits:
checkout
selection
(protection 2)
0: untested
1: Detecting excessive loads
2: Overload detection at
constant speed only
3: Detecting insufficient
load
4: Insufficient load detection
at constant speed only
LED thousand digits: alarm
selection
0: Alarm, continue to run
1: Fail-safe operation and
free stop
0000
〇
△
0xA11
FA.18
Load
warning
detection level1
0.0%~200.0%
130.0%
〇
△
0xA12
FA.19
Load
warning
detection time1
0.0s~60.0s
5.0s
〇
△
0xA13
FA.20
Load
warning
detection level2
0.0%~200.0%
30.0%
〇
△
0xA14
FA.21
Load
warning
detection time2
0.0s~60.0s
5.0s
〇
△
0xA15
FA.22
Input
out-of-
phase threshold
0.0%~30.0%
10.0%
〇
0xA16