Chapter 8 Functional Parameter Table
ACH200 Series High Voltage Variable Frequency Speed Control System Operating Manual
75
Chapter 8 Functional Parameter Table
“●” : Indicates that this parameter can be changed when the AC drive is in operation
;
“
〇
” : Indicates that the parameter cannot be changed when the AC drive is in operation
;
“×” : Indicates that the parameter can only be read, not changed
;
“–” : Indicates that the parameter is a "factory parameter" and is limited to factory settings
;
“※” : Indicates that the parameter is related to the model of the AC drive
;
“▲” : Indicates that the parameter is valid only in rectifier mode, not in AC drive
;
“
△
” : Indicates that the parameter is valid only in AC drive mode and not in rectifier mode
。
Note: The parameter codes not marked with "
△
" and "▲" indicate no specific distinction between
rectifier and AC drive modes.
8.1 Summary Table of Basic Functional Parameters
8.1.1 F0 Basic Parameter Group
Functi
on
Code
Function code
name
Setting value range and
definition
Factory
settings
Prop
erties
Address
F0.00
Motor control
method
Asynchronous motor control
mode:
0: V/F control
1: Reserved
2: Reserved
3: PG-free high-performance
vector control
4: High performance vector
control with PG
Synchronous motor control
mode:
5: Reserved
6: PG-free high-performance
vector control
7: With PG vector control
Other control modes:
8: Voltage and frequency
separated output
0
〇
△
0x000